prev 8 / 30page next
  • Output frequency

    In the initial setting, it is set to 120 Hz. More Details >>

    • No:21345
    • Release Date:2018/08/22 16:27
  • Fault output terminal A, B, and C

    Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>

    • No:21324
    • Release Date:2018/08/22 16:27
  • Start command

    Set Pr.338 (Communication command source) to "0" to give a start command from "NET". Set Pr.339 (Speed command source) to "1" to make a frequency setting fro... More Details >>

    • No:21285
    • Release Date:2018/08/22 16:26
  • Frequency meter

    First, check if Pr.55 (Frequency monitor reference) that is the reference for the FM output is set correctly.Next, operate the inverter (without connecting a... More Details >>

    • No:21808
    • Release Date:2018/08/22 16:29
  • Frequency setting

    When the potentiometer is disconnected and frequency commands cease, the input potential becomes around 0 V.Therefore, the frequency command becomes analog-c... More Details >>

    • No:21794
    • Release Date:2018/08/22 16:29
  • Minimum frequency

    If any other frequency is not set, when the start signal is input, the inverter starts acceleration from 0.5 Hz set with Pr.13 (Starting frequency) up to 3 H... More Details >>

    • No:21777
    • Release Date:2018/08/22 16:29
  • Electromagnetic contactor

    Turning ON/OFF the output side during operation causes open/close surges that may trigger the protective function (against overcurrent or overvoltage) of the... More Details >>

    • No:21725
    • Release Date:2018/08/22 16:29
  • Life diagnosis

    When Pr.259 (Main circuit capacitor life measuring) is set to "1", the life diagnosis is ready. Turning OFF the power supply starts measuring the life of the... More Details >>

    • No:21283
    • Release Date:2018/08/22 16:26
  • CC-Link

    Use Pr.542 to set the station number and Pr.543 to set the baud rate.To set the baud rate to 10 Mbps, set Pr.543 to "4". More Details >>

    • No:21839
    • Release Date:2018/08/22 16:29
  • Running frequency

    Check the setting of Pr.1 (Maximum frequency) and Pr.18 (High speed maximum frequency).Pr.1 is initially set to "120 Hz". More Details >>

    • No:21821
    • Release Date:2018/08/22 16:29