FAQ
![](/usr/file/attachment/q&a.jpg)
![](/usr/file/attachment/q&a_sp.jpg)
FAQAbout Products
![](/usr/file/attachment/img_mv-1_sm.jpg)
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F700
FAQ
Keyword Search
FAQ within [ FREQROL-F700 ]
-
Set Pr.338 to "0" (NET) and Pr.339 to "1" or "2". More Details >>
- No:21674
- Release Date:2018/08/22 16:28
-
The parameter setting software we provide is the FR Configurator (FR-SW3-SETUP-WJ). You must purchase it to use. Once you purchase the software, you can upgr... More Details >>
- No:21673
- Release Date:2018/08/22 16:28
-
The forward rotation and reverse rotation are enabled by pressing the FWD/REV key on the operation panel. More Details >>
- No:21364
- Release Date:2018/08/22 16:27
-
There are two methods to reduce the running frequency variation. 1. Increase the setting value of Pr.74 (Input filter time constant) to reduce the variation.... More Details >>
- No:21296
- Release Date:2018/08/22 16:26
-
Set Pr.338 (Communication command source) to "0" to give a start command from "NET". Set Pr.339 (Speed command source) to "1" to make a frequency setting fro... More Details >>
- No:21285
- Release Date:2018/08/22 16:26
-
Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>
- No:21280
- Release Date:2018/08/22 16:26
-
The FR-A5AY cannot be used in the FR-A700 (F700(P)). It cannot be installed due to the difference of the connector shape. More Details >>
- No:21260
- Release Date:2018/08/22 16:26
-
With the automatic bypass sequence (Pr.139 ≠ 9999, Pr.159 = 9999), the motor operation is switched to commercial power supply operation when the output frequ... More Details >>
- No:21189
- Release Date:2018/08/22 16:26
-
For countermeasures against the open/close surge of the MC (magnetic contactor). Insert a diode not to apply 27 VDC or more to the open collector terminal of... More Details >>
- No:21188
- Release Date:2018/08/22 16:26
-
Removal of the jumper between the terminals P1 and P is not necessary unless you are using the DC reactor.Set Pr.30 = "0" when using the brake unit.Since set... More Details >>
- No:21921
- Release Date:2018/08/22 16:30
71-80 of Total 296