  • NET mode, external operation switching

    You can switch between the NET mode and external operation.Assign the X66 signal (Operation switching) to an unused terminal for switching.Also, set Pr.79 (O... More Details >>

    • No:21906
    • Release Date:2018/08/22 16:30
  • Network operation

    Yes. With the setting "66", you can choose NET operation when X66 is ON, and external operation when X66 is OFF. More Details >>

    • No:21675
    • Release Date:2018/08/22 16:28
  • CC-Link

    To set the frequency via CC-Link communication, the NET mode should be selected. The new parameter setting is applied after powering OFF and then ON the inve... More Details >>

    • No:21763
    • Release Date:2018/08/22 16:29
  • CC-Link

    Yes.You can issue operation (forward/reverse), frequency setting, parameter read/write, and operation monitor commands. More Details >>

    • No:21899
    • Release Date:2018/08/22 16:29
  • FR-PA07

    Operations cannot be enabled separately. You only can disable or enable all the operations. More Details >>

    • No:21366
    • Release Date:2018/08/22 16:27
  • CC-Link

    You can set reserved and invalid stations.The Instruction Manual instructs to set consecutive numbers because the master regards an empty number as an error. More Details >>

    • No:21905
    • Release Date:2018/08/22 16:30
  • CC-Link

    You can select deceleration stop by setting Pr.502 (Stop mode selection at communication error). (Select from coasting to stop, deceleration to stop, and con... More Details >>

    • No:21892
    • Release Date:2018/08/22 16:29
  • Frequency setting

    When the potentiometer is disconnected and frequency commands cease, the input potential becomes around 0 V.Therefore, the frequency command becomes analog-c... More Details >>

    • No:21794
    • Release Date:2018/08/22 16:29
  • CC-Link communication

    After setting Pr.79 (Operation mode selection) to "2" and Pr.340 (Communication startup mode selection) to "10", reset the inverter (or power ON again) to st... More Details >>

    • No:21256
    • Release Date:2018/08/22 16:26
  • Output current

    Increasing the value of Pr.0 (Torque boost) increases the output voltage, and the output current also increases.Note that increasing this value too high puts... More Details >>

    • No:21732
    • Release Date:2018/08/22 16:29