  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29
  • Motor specifications setting

    Yes.Set Pr.19 (Base frequency voltage) to "200 V".200 V output will be obtained during 60 Hz operation. More Details >>

    • No:21717
    • Release Date:2018/08/22 16:29
  • Parameter setting

    Yes. The single-phase 200 V can be input. If the single-phase input is performed when Pr.872 (Input phase loss protection) is set to "1", the input phase los... More Details >>

    • No:21270
    • Release Date:2018/08/22 16:26
  • Parameter read

    By setting Pr.160 (User group read selection ("Extended function display selection" for D700)) to "0", all the parameters can be read. More Details >>

    • No:21262
    • Release Date:2018/08/22 16:26
  • CC-Link communication

    After setting Pr.79 (Operation mode selection) to "2" and Pr.340 (Communication startup mode selection) to "10", reset the inverter (or power ON again) to st... More Details >>

    • No:21256
    • Release Date:2018/08/22 16:26
  • Frequency setting

    The full scale of the frequency is initially set to 60 Hz and the frequency indication becomes the full scale at 60 Hz operation.To change the indication val... More Details >>

    • No:21866
    • Release Date:2018/08/22 16:29
  • Terminal FM

    Set Pr.56 (Current monitor reference) to "10A". More Details >>

    • No:21865
    • Release Date:2018/08/22 16:29
  • CC-Link station number setting

    Change the setting in the PU operation mode.   More Details >>

    • No:21747
    • Release Date:2018/08/22 16:29
  • Speed setting

    Use the inverter's calibration parameters Pr.C2/C3, Pr.125/C4 to adjust the bias and gain for each inverter.Connect the wires from the frequency setting pote... More Details >>

    • No:21728
    • Release Date:2018/08/22 16:29
  • Monitor indicator

    No. You cannot check the accumulated number of rotations on the monitor.   More Details >>

    • No:21715
    • Release Date:2018/08/22 16:29