The internal processing speed is not published. The analog input specifications are as follows: FR-A500???1/4000FR-E500???1/1000MR-H???1/4000 More Details >>
- No:21550
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
Heat generation quantity of FR-A500
The heat generation quantity of the FR-A520-5.5K is 310 W. (Reference: The heat generation quantity of the FR-A220E-5.5K is 330 W.) For other capacities, ref... More Details >>
- No:21515
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Refer to the following points.For fan pump -> Square torqueFor general-purpose machine (for example, transport, elevation) -> Constant-torque type More Details >>
- No:22048
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
To conform to the EMC Directive when exporting to an EU country, install the filter that conforms to the EMC Directive on the inverter, and take measures acc... More Details >>
- No:21414
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Functions available when using inverter on CC-Link
You can use the regular terminal block wire functions during CC-Link operation. Set Pr.338 (Operation command source) and Pr.339 (Speed command source) to e... More Details >>
- No:21393
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Remote operation of the inverter
The wiring length of the start signal (STF etc.) is 30 m or less. The circuit voltage of the control input signals (terminal STF etc.) is 24 VDC and the volt... More Details >>
- No:21380
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
If the phase A and phase B are connected reversely, encoder feedback control is not performed. Instead, the inverter is operated in normal control (V/F contr... More Details >>
- No:21524
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Use the first contact (relay) for the forward (or reverse) rotation between the terminals STF and SD. Use the second contact (relay) for the high-speed comma... More Details >>
- No:21472
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Durability in multi-speed setting
1. You can set the minimum time by setting the acceleration/deceleration time and acceleration/deceleration reference frequency. 2. No problem with the termi... More Details >>
- No:21437
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Is the number of writing times of the parameter memory limited?
1. The limit of the parameter writing is 100,000 times. 2. Parameter error occurs. Since the data in the ROM may be broken, the inverter may become unavailab... More Details >>
- No:21385
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
91-100 of Total 123