FREQROL-A500
FAQ within [ FREQROL-A500 ]
-
1. You can implement stop-on-contact.2. When implementing stop-on-contact, use the inverter to decelerate the motors to reduce the impact upon stop-on-contac... More Details >>
- No:22041
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Motor heat generation at low-speed operation
When using the FR-A540-3.7K in Advanced magnetic flux vector control, operating the motor continuously under the 100% torque at up to 3 Hz does not cause a h... More Details >>
- No:21496
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
1. The inverter display is based on the frequency, and the speed and moving speed are displayed by converting the frequency into the corresponding value. The... More Details >>
- No:21480
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Use the first contact (relay) for the forward (or reverse) rotation between the terminals STF and SD. Use the second contact (relay) for the high-speed comma... More Details >>
- No:21472
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Installing magnetic contactor on input side of inverter
Basically, there is no difference between the A200 and A500. For safer use, from the A500, it is recommended to completely shut off the power supply by turni... More Details >>
- No:21466
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Using shielded wires for frequency meter connection
Connect the shield to the terminal SD. More Details >>
- No:22034
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
If you connect two frequency setting potentiometers to the terminals 5 and 10, the permissible current of 10 mA is exceeded, and you need to install 2 KΩ res... More Details >>
- No:21494
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
When the inverter output shutoff signal MRS is turned on, the output is shut off immediately without regard to setting of Pr.250. More Details >>
- No:21423
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
This error is displayed when the inverter and operation panel FR-PU04 cannot communicate with each other correctly or the reset signal remains ON. Therefore,... More Details >>
- No:21546
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Heat generation quantity of FR-A500
The heat generation quantity of the FR-A520-5.5K is 310 W. (Reference: The heat generation quantity of the FR-A220E-5.5K is 330 W.) For other capacities, ref... More Details >>
- No:21515
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500