Since the terminal FM is designed with 8 V peak pulse voltage output, it cannot output 10 V.Since the terminal AM is an analog output of 0 V to 10 V, use thi... More Details >>
- No:21978
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Concurrent monitoring of running frequency, output voltage, and output current
Add an analog output by the FR-A5AY.Monitor the three output; output AM (0 to 5 (10) V) and optional 4 to 20 mA, and 0 to 5 (10) V. More Details >>
- No:21959
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-F500
-
Since a large load is applied to the motor when the electromagnetic clutch turns on, overcurrent may occur if the load is heavy. To ensure that the rated cur... More Details >>
- No:21955
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
Faults history upon power failure
When an instantaneous power failure of 100 msec or longer occurs, the inverter is reset* and it is not recognized as a fault. Since it is not recognized as a... More Details >>
- No:21551
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
The internal processing speed is not published. The analog input specifications are as follows: FR-A500???1/4000FR-E500???1/1000MR-H???1/4000 More Details >>
- No:21550
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
This error is displayed when the inverter and operation panel FR-PU04 cannot communicate with each other correctly or the reset signal remains ON. Therefore,... More Details >>
- No:21546
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
You cannot disable the error display. The OC1 overcurrent alarm is displayed. The condition to display this alarm is that the main circuit power supply is OF... More Details >>
- No:21535
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
If the phase A and phase B are connected reversely, encoder feedback control is not performed. Instead, the inverter is operated in normal control (V/F contr... More Details >>
- No:21524
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
The inverter (FR-A520-5.5K) itself generates approximately 310 W of heat. This is the amount generated under the inverter rated current 100% load. Since the ... More Details >>
- No:21523
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Heat generation quantity of FR-A500
The heat generation quantity of the FR-A520-5.5K is 310 W. (Reference: The heat generation quantity of the FR-A220E-5.5K is 330 W.) For other capacities, ref... More Details >>