Since the terminal FM is designed with 8 V peak pulse voltage output, it cannot output 10 V.Since the terminal AM is an analog output of 0 V to 10 V, use thi... More Details >>
- No:21978
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Load current limit of inverter
You can input current from the terminal AM of the inverter to the programmable controller (for A/D conversion) and control the speed with the software of the... More Details >>
- No:21419
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Installation clearance of inverters
Keep 1 cm or more of clearance for 3.7 K or smaller, and 5 cm or more for 5.5 K or larger.If the clearance is too small, the cooling effect is lowered. Secur... More Details >>
- No:22046
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Calculation of inverter acceleration and deceleration time
Refer to the Technical Sheet No.23 (Capacity Selection and Continuous Operation) for reference for selection. Optional capacity selection software is also pr... More Details >>
- No:22097
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Digital input and maximum frequency
1. Pr.1 and 18 limit the output to 120 Hz. Use Pr.18 to change the maximum frequency. 2. If you want to output the binary input as is, setting Pr.304 = 1 (Bi... More Details >>
- No:22098
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Plug-in Options , FREQROL-A500
-
UL standard certification number
The UL standard certification numbers (UL Listing Card No.) of the FR-E500, FR-A500, and FR-A200 are as follows: FR-A200 series??????E131592FR-A500 series???... More Details >>
- No:21506
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500 , FREQROL-A200
-
Using the inverter's input terminal, you can use up to 15 speeds.This function is supported by the current 500 series products (A500, F500, E500, and S500).U... More Details >>
- No:21947
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-F500 , FREQROL-E500 , FREQROL-S500
-
It can be used in terms of the specifications. However, it is recommended to update the reactor and inverter at the same time because the DC reactor was manu... More Details >>
- No:21017
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , Inverters-FREQROL , FREQROL-F800 , FREQROL-A500 , FREQROL-F500
-
If the output current is close to 25% of the rated current, output phase loss may occur when one or two phases of three phases go below 25%.Therefore, when a... More Details >>
- No:22052
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
Automatic overload control of inverter
The inverter has the current limit function. This automatically controls the frequency so that the preset current value may not be exceeded. (Note that the m... More Details >>