FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-A500
FAQ
Keyword Search
FREQROL-A500
FAQ within [ FREQROL-A500 ]
-
1. By changing RWw1 while RYD is ON, you can change the inverter's frequency.You cannot do this with RYE. You need to turn OFF and then ON RYE each time you ... More Details >>
- No:22083
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Since the brake sequence function requires Advanced magnetic flux vector control and advanced flux control is applied to 0.4 kW or higher motors, you cannot ... More Details >>
- No:22075
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
All parameters returned to initial values
The parameters of the A500 series are stored in the EEPROM.The reason why all parameters returned to the initial values is considered that you may have opera... More Details >>
- No:22066
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Pulse train output of terminal FM
Under Advanced magnetic flux vector control, the output frequency varies due to slip compensation. This may cause the output frequency monitor value to chang... More Details >>
- No:22054
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
As an example, you can use an inverter to feed the cord at the constant speed under dancer control using a combination of the deviation detector and deviatio... More Details >>
- No:22047
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Using shielded wires for frequency meter connection
Connect the shield to the terminal SD. More Details >>
- No:22034
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
FR-A500 main circuit wire types
Since the UL standard defines to "Use copper wires (rated at 75?C)", we also recommend the same type of copper wire. More Details >>
- No:22032
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Driving two motors with different capacities
It is OK to drive motors by switching the electromagnetic contactor on the inverter's output side.It is also OK if the motor capacity is small. However, if t... More Details >>
- No:22022
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Speed precision of Advanced magnetic flux vector control
The speed precision for each model is as follows:FR-K440 with PG: 1% or less of the maximum speed (3500 rpm)FR-A540 without PG (Advanced flux vector): 1% or ... More Details >>
- No:22013
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
They are capable of a load of 5 VDC±5% and 10 mA. More Details >>
- No:21977
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
101-110 of Total 123