Using FR-A540 inverter on CC-Link
Answer to question 1 When the CC-Link option goes faulty, OPT (option error) occurs and the inverter's fault output is triggered. When communication is lost ... More Details >>
Countermeasures when input power supp...
1. When the inverter power supply is turned OFF, the inverter is disconnected from the CC-Link network. However, since the CC-Link master station has the aut... More Details >>
Is the number of writing times of the...
1. The limit of the parameter writing is 100,000 times. 2. Parameter error occurs. Since the data in the ROM may be broken, the inverter may become unavailab... More Details >>
Inverter UL and CSA standard product ...
The certificate of the standard product is managed by the branch office. Please ask the nearest branch office. More Details >>
Remote operation of the inverter
The wiring length of the start signal (STF etc.) is 30 m or less. The circuit voltage of the control input signals (terminal STF etc.) is 24 VDC and the volt... More Details >>
The current monitor displays the average value of the three-phase current. The three-phase voltage is not incorporated for the voltage monitor. The output vo... More Details >>
Operation of the motor with a brake
For the general-purpose inverter, the motor stop cannot be detected accurately because the actual motor speed from a motor is not input. In general, the RUN ... More Details >>
When Advanced magnetic flux vector control (Pr.80, 81) is used, the machine speed constant is controlled. The inverter calculates the motor slip and compensa... More Details >>
After inputting the start signal performing the tuning, output the output frequency. The tuning ends in approximately 500 ms in maximum after started. Durin... More Details >>
Vector control of the inverter
The speed fluctuation ratio under Advanced magnetic flux vector control of the FR-A500 is as follows. Without encoder: ±1% With encoder (with A5AP): ±0. 02 %... More Details >>