FREQROL-A500
FAQ within [ FREQROL-A500 ]
-
Use the first contact (relay) for the forward (or reverse) rotation between the terminals STF and SD. Use the second contact (relay) for the high-speed comma... More Details >>
- No:21472
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Inverter operation against power supply voltage drop
Depending on the load current, undervoltage protection (UVT) or instantaneous power failure protection (IPF) is triggered to shut off the inverter output, an... More Details >>
- No:21471
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
When Advanced magnetic flux vector control (Pr.80, 81) is used, the machine speed constant is controlled. The inverter calculates the motor slip and compensa... More Details >>
- No:21374
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Vector control of the inverter
The speed fluctuation ratio under Advanced magnetic flux vector control of the FR-A500 is as follows. Without encoder: ±1% With encoder (with A5AP): ±0. 02 %... More Details >>
- No:21369
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
The inverter (FR-A520-5.5K) itself generates approximately 310 W of heat. This is the amount generated under the inverter rated current 100% load. Since the ... More Details >>
- No:21523
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Faults history upon power failure
When an instantaneous power failure of 100 msec or longer occurs, the inverter is reset* and it is not recognized as a fault. Since it is not recognized as a... More Details >>
- No:21551
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Torque characteristic at low speed
Torque is not guaranteed for slower than 0.5 Hz. Therefore, no data for this is published. Also, no torque is generated at 0 Hz. More Details >>
- No:21543
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Simple torque control using stall prevention function
Basically, torque control cannot be performed. Instead, control speed to adjust the winding torque. It is possible to use the current limit function to preve... More Details >>
- No:21493
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
To conform to the EMC Directive when exporting to an EU country, install the filter that conforms to the EMC Directive on the inverter, and take measures acc... More Details >>
- No:21414
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500