FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-A500
FAQ
Keyword Search
FREQROL-A500
FAQ within [ FREQROL-A500 ]
-
Operation of automatic restart after instantaneous power failure
1. No operation log is recorded.2. No. However, you can create a state indicating that automatic restart after instantaneous power failure is in progress by ... More Details >>
- No:21948
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Change Pr.18 (High speed maximum frequency) to 400 Hz.If you are using the analog command to set the frequency, calibrate the 400 Hz frequency with Pr.903. More Details >>
- No:21931
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Countermeasure against oil mist
1. You cannot use the inverter in an environment where it is exposed to oil mist. You need to enclose the inverter in an enclosure and then install the encl... More Details >>
- No:21538
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Countermeasure against the fault occurrence
When a CC-Link communication fault occurs, the option error (OP3) occurs on the inverter and the output is shut off, and the motor starts coasting. When usin... More Details >>
- No:21531
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
The inverter (FR-A520-5.5K) itself generates approximately 310 W of heat. This is the amount generated under the inverter rated current 100% load. Since the ... More Details >>
- No:21523
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Heat generation quantity of FR-A500
The heat generation quantity of the FR-A520-5.5K is 310 W. (Reference: The heat generation quantity of the FR-A220E-5.5K is 330 W.) For other capacities, ref... More Details >>
- No:21515
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
If you connect two frequency setting potentiometers to the terminals 5 and 10, the permissible current of 10 mA is exceeded, and you need to install 2 KΩ res... More Details >>
- No:21494
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Simple torque control using stall prevention function
Basically, torque control cannot be performed. Instead, control speed to adjust the winding torque. It is possible to use the current limit function to preve... More Details >>
- No:21493
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Use the first contact (relay) for the forward (or reverse) rotation between the terminals STF and SD. Use the second contact (relay) for the high-speed comma... More Details >>
- No:21472
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Since the stall prevention function works during acceleration and the inverter does not reach the commanded speed, set Pr.156 (Stall prevention operation sel... More Details >>
- No:21460
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
111-120 of Total 123