FREQROL-A500
FAQ within [ FREQROL-A500 ]
-
Countermeasure against oil mist
1. You cannot use the inverter in an environment where it is exposed to oil mist. You need to enclose the inverter in an enclosure and then install the encl... More Details >>
- No:21538
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Is the number of writing times of the parameter memory limited?
1. The limit of the parameter writing is 100,000 times. 2. Parameter error occurs. Since the data in the ROM may be broken, the inverter may become unavailab... More Details >>
- No:21385
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
When the inverter output shutoff signal MRS is turned on, the output is shut off immediately without regard to setting of Pr.250. More Details >>
- No:21423
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
After inputting the start signal performing the tuning, output the output frequency. The tuning ends in approximately 500 ms in maximum after started. Durin... More Details >>
- No:21372
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Functions available when using inverter on CC-Link
You can use the regular terminal block wire functions during CC-Link operation. Set Pr.338 (Operation command source) and Pr.339 (Speed command source) to e... More Details >>
- No:21393
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Installing magnetic contactor on input side of inverter
Basically, there is no difference between the A200 and A500. For safer use, from the A500, it is recommended to completely shut off the power supply by turni... More Details >>
- No:21466
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Operation of the motor with a brake
For the general-purpose inverter, the motor stop cannot be detected accurately because the actual motor speed from a motor is not input. In general, the RUN ... More Details >>
- No:21375
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Using FR-A540 inverter on CC-Link
Answer to question 1 When the CC-Link option goes faulty, OPT (option error) occurs and the inverter's fault output is triggered. When communication is lost ... More Details >>
- No:21391
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
If you connect two frequency setting potentiometers to the terminals 5 and 10, the permissible current of 10 mA is exceeded, and you need to install 2 KΩ res... More Details >>
- No:21494
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Countermeasure against the fault occurrence
When a CC-Link communication fault occurs, the option error (OP3) occurs on the inverter and the output is shut off, and the motor starts coasting. When usin... More Details >>
- No:21531
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500