Which is the recommended digital counter?
We recommend the following digital counter: (Connect it between the terminals FM and SD.) Manufacturer: KOYO ELECTRONICS INDUSTRIES CO., LTD.Model: TC-41 More Details >>
- No:21469
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Others , FREQROL-A500
-
Controlling multiple VVVFs via communication from personal computer
To control multiple inverters using arbitrary signals (4 to 20 mA) simultaneously, it is recommended to connect the signals (4 to 20 mA) in series. (This doe... More Details >>
- No:21491
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
The inverter (FR-A520-5.5K) itself generates approximately 310 W of heat. This is the amount generated under the inverter rated current 100% load. Since the ... More Details >>
- No:21523
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Countermeasure against the fault occurrence
When a CC-Link communication fault occurs, the option error (OP3) occurs on the inverter and the output is shut off, and the motor starts coasting. When usin... More Details >>
- No:21531
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Term definition and advanced magnetic flux control
1. Maximum torque available for output from the motor when combined with an inverter for a short period of time (1 minute or less). It depends on the contr... More Details >>
- No:21541
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Torque characteristic at low speed
Torque is not guaranteed for slower than 0.5 Hz. Therefore, no data for this is published. Also, no torque is generated at 0 Hz. More Details >>
- No:21543
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Faults history upon power failure
When an instantaneous power failure of 100 msec or longer occurs, the inverter is reset* and it is not recognized as a fault. Since it is not recognized as a... More Details >>
- No:21551
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Since the terminal FM is designed with 8 V peak pulse voltage output, it cannot output 10 V.Since the terminal AM is an analog output of 0 V to 10 V, use thi... More Details >>
- No:21978
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Two-rank up maximum short-time torque
It is not possible to generate torque larger than the maximum possible torque of the motor by increasing the inverter's capacity.Even when the inverter is up... More Details >>
- No:22027
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
FR-A500 main circuit wire types
Since the UL standard defines to "Use copper wires (rated at 75?C)", we also recommend the same type of copper wire. More Details >>
- No:22032
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
11-20 of Total 119