Speed control failure due to 20 mA from DC 4
It seems that there is a read error for 20 mA DC inside the inverter.Setting Pr.905 to 50 Hz while 20 mA DC is actually flowing between the terminals 4 and 5... More Details >>
- No:21998
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-F500 , FREQROL-E500 , FREQROL-A200 , FREQROL-A100
-
Driving 200 V motor by 400 V inverter
A 400 V inverter does not operate when 200 V is supplied to it, therefore the motor does not rotate. A 200 V motor can be rotated by a 400 V inverter, howeve... More Details >>
- No:21446
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-A024 , FREQROL-V200 , FREQROL-A200 , FREQROL-A100
-
Automatic overload control of inverter
The inverter has the current limit function. This automatically controls the frequency so that the preset current value may not be exceeded. (Note that the m... More Details >>
- No:21409
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-F500 , FREQROL-E500 , FREQROL-S500
-
Using the inverter's input terminal, you can use up to 15 speeds.This function is supported by the current 500 series products (A500, F500, E500, and S500).U... More Details >>
- No:21947
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-F500 , FREQROL-E500 , FREQROL-S500
-
Impossible to recover after power failure
First, ensure that the parameter for automatic restart after instantaneous power failure is set correctly and then do the following:1. Check if the terminals... More Details >>
- No:22033
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Output side earth (ground) fault overcurrent protection
1. How much is the sensitivity current? When the sum of the three-phase output current of the inverter reaches approximately 70% of the inverter rated curren... More Details >>
- No:21394
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-A024 , FREQROL-E500
-
Digital input and maximum frequency
1. Pr.1 and 18 limit the output to 120 Hz. Use Pr.18 to change the maximum frequency. 2. If you want to output the binary input as is, setting Pr.304 = 1 (Bi... More Details >>
- No:22098
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Plug-in Options , FREQROL-A500
-
UL standard certification number
The UL standard certification numbers (UL Listing Card No.) of the FR-E500, FR-A500, and FR-A200 are as follows: FR-A200 series??????E131592FR-A500 series???... More Details >>
- No:21506
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500 , FREQROL-A200
-
Resetting inverter after restoring from power failure
When the programmable controller power is turned OFF while the inverter is in the PLC link operation mode, a communication error occurs and the inverter trip... More Details >>
- No:21417
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Plug-in Options , FREQROL-A500
-
Pr.133 can be written.Since the data code numbers of parameters are duplicate, target parameters are switched by link parameter extended setting.You can acce... More Details >>
- No:21976
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Plug-in Options , FREQROL-A500 , FREQROL-F500