FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-A500
FAQ
Keyword Search
FREQROL-A500
FAQ within [ FREQROL-A500 ]
-
Installing magnetic contactor on input side of inverter
Basically, there is no difference between the A200 and A500. For safer use, from the A500, it is recommended to completely shut off the power supply by turni... More Details >>
- No:21466
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Using FR-A540 inverter on CC-Link
Answer to question 1 When the CC-Link option goes faulty, OPT (option error) occurs and the inverter's fault output is triggered. When communication is lost ... More Details >>
- No:21391
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
To conform to the EMC Directive when exporting to an EU country, install the filter that conforms to the EMC Directive on the inverter, and take measures acc... More Details >>
- No:21414
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Countermeasure against oil mist
1. You cannot use the inverter in an environment where it is exposed to oil mist. You need to enclose the inverter in an enclosure and then install the encl... More Details >>
- No:21538
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Change Pr.18 (High speed maximum frequency) to 400 Hz.If you are using the analog command to set the frequency, calibrate the 400 Hz frequency with Pr.903. More Details >>
- No:21931
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
FR-A500 main circuit wire types
Since the UL standard defines to "Use copper wires (rated at 75?C)", we also recommend the same type of copper wire. More Details >>
- No:22032
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Reset command during operation
The reset signal does not damage the inverter.It seems that the inverter went faulty due to other reasons.Mitsubishi Electric FA Center can inspect the inver... More Details >>
- No:22065
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Inverter stop-on-contact control
Use the FREQROL-A500 series inverter with the optional FR-A5NC.Then, you can implement both of stop-on-contact control and CC-Link operation. More Details >>
- No:22089
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Check if the communication setting parameters (Pr.117 to Pr.124) are set to the same values between the inverter and personal computer.Note that communicatio... More Details >>
- No:22105
- Release Date:2018/08/22 16:31
- Category: Inverters-FREQROL , FREQROL-A500
-
Outgoing harmonic current (0.1 kW, 0.2 kW)
200 V, 0.1 kW to 3.7 kW products are subject to regulation by the harmonic suppression guidelines for household appliances and general-purpose products. Ther... More Details >>
- No:21444
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
21-30 of Total 119