1. By changing RWw1 while RYD is ON, you can change the inverter's frequency.You cannot do this with RYE. You need to turn OFF and then ON RYE each time you ... More Details >>
- No:22083
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
This error is displayed when the inverter and operation panel FR-PU04 cannot communicate with each other correctly or the reset signal remains ON. Therefore,... More Details >>
- No:21546
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Change Pr.18 (High speed maximum frequency) to 400 Hz.If you are using the analog command to set the frequency, calibrate the 400 Hz frequency with Pr.903. More Details >>
- No:21931
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
FR-A500 main circuit wire types
Since the UL standard defines to "Use copper wires (rated at 75?C)", we also recommend the same type of copper wire. More Details >>
- No:22032
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Impossible to recover after power failure
First, ensure that the parameter for automatic restart after instantaneous power failure is set correctly and then do the following:1. Check if the terminals... More Details >>
- No:22033
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Reset command during operation
The reset signal does not damage the inverter.It seems that the inverter went faulty due to other reasons.Mitsubishi Electric FA Center can inspect the inver... More Details >>
- No:22065
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Inverter stop-on-contact control
Use the FREQROL-A500 series inverter with the optional FR-A5NC.Then, you can implement both of stop-on-contact control and CC-Link operation. More Details >>
- No:22089
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Items controllable via CC-Link
1. Not all items can be controlled. - Functions that cannot be controlled JOG, AU, CS, OH, X10, X11, X12, and X16 functions (Other functions can be control... More Details >>
- No:21459
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
Which is the recommended digital counter?
We recommend the following digital counter: (Connect it between the terminals FM and SD.) Manufacturer: KOYO ELECTRONICS INDUSTRIES CO., LTD.Model: TC-41 More Details >>
- No:21469
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Others , FREQROL-A500
-
Faults history upon power failure
When an instantaneous power failure of 100 msec or longer occurs, the inverter is reset* and it is not recognized as a fault. Since it is not recognized as a... More Details >>
- No:21551
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
21-30 of Total 119