FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-A500
FAQ
Keyword Search
FREQROL-A500
FAQ within [ FREQROL-A500 ]
-
No. Check the parameter setting of the A500(L), and then adjust the parameter setting of the A800 to those of the A500(L). For the details, refer to the repl... More Details >>
- No:21108
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , FREQROL-A500
-
1. To perform emergency stop, it is recommended to have the motor coast and stop it using a mechanical brake.In this case, the output stop (MRS) signal is in... More Details >>
- No:22103
- Release Date:2018/08/22 16:31
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
Output phase loss protection error
- How to find out lost phaseMeasure the three-phase current when the error has occurred.The phase with a small (or no) phase current is lost.- Possibility of... More Details >>
- No:21969
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Use the FR-AAT04 (FR-Z series intercompatibility attachment). More Details >>
- No:21928
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-Z300
-
Although you specify the FR-V200 and others as the inverter models, CC-Link is currently supported by the FR-A500 and FR-E500. The FR-V200E does not support ... More Details >>
- No:21499
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
Motor heat generation at low-speed operation
When using the FR-A540-3.7K in Advanced magnetic flux vector control, operating the motor continuously under the 100% torque at up to 3 Hz does not cause a h... More Details >>
- No:21496
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Inverter operation at instantaneous power failure
When performing the automatic restart after instantaneous power failure, input the operation signal (STF or STR) and selection of automatic restart after ins... More Details >>
- No:21371
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
All parameters returned to initial values
The parameters of the A500 series are stored in the EEPROM.The reason why all parameters returned to the initial values is considered that you may have opera... More Details >>
- No:22066
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
External wiring for CC-Link operation
For the combination of the FR-A500 + FR-A5NC, Pr.338 and Pr.339 are used to specify whether the external signals or CC-Link commands are used to set the runn... More Details >>
- No:21973
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
How can I calculate the processing torque from the measured power?
You can calculate the torque from the power. From the general equation: Pout = ωn × TT = (Pout × τ)/ωnPout: Measured valueωn: Actual motor shaft angular fre... More Details >>
- No:21475
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Others , FREQROL-A500