FAQ


FAQAbout Products

- FAQ > Drive Products > Inverters-FREQROL > FREQROL-A500
FAQ
Keyword Search
FREQROL-A500
FAQ within [ FREQROL-A500 ]
-
Is the number of writing times of the parameter memory limited?
1. The limit of the parameter writing is 100,000 times. 2. Parameter error occurs. Since the data in the ROM may be broken, the inverter may become unavailab... More Details >>
- No:21385
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Functions available when using inverter on CC-Link
You can use the regular terminal block wire functions during CC-Link operation. Set Pr.338 (Operation command source) and Pr.339 (Speed command source) to e... More Details >>
- No:21393
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Selection of high-duty brake resistor
Select the high-duty brake resistor according to the inverter capacity. More Details >>
- No:21953
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
They are capable of a load of 5 VDC±5% and 10 mA. More Details >>
- No:21977
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
There is a 10 ms delay after the inverter recognizes the start command (STF OR STR) before it starts decelerating. The delay is 10 ms. A delay of 100 ms is i... More Details >>
- No:21445
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Inverter stop-on-contact control
Use the FREQROL-A500 series inverter with the optional FR-A5NC.Then, you can implement both of stop-on-contact control and CC-Link operation. More Details >>
- No:22089
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Operation by single-phase power supply
Similarly to the FR-A220, single-phase power supply operation is possible by reducing the inverter's output current.Ensure that the output current is smaller... More Details >>
- No:22107
- Release Date:2018/08/22 16:31
- Category: Inverters-FREQROL , FREQROL-A500
-
Operation of the motor with a brake
For the general-purpose inverter, the motor stop cannot be detected accurately because the actual motor speed from a motor is not input. In general, the RUN ... More Details >>
- No:21375
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Countermeasure against the fault occurrence
When a CC-Link communication fault occurs, the option error (OP3) occurs on the inverter and the output is shut off, and the motor starts coasting. When usin... More Details >>
- No:21531
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Countermeasure against oil mist
1. You cannot use the inverter in an environment where it is exposed to oil mist. You need to enclose the inverter in an enclosure and then install the encl... More Details >>
- No:21538
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
71-80 of Total 123