If the phase A and phase B are connected reversely, encoder feedback control is not performed. Instead, the inverter is operated in normal control (V/F contr... More Details >>
The inverter (FR-A520-5.5K) itself generates approximately 310 W of heat. This is the amount generated under the inverter rated current 100% load. Since the ... More Details >>
Installation dimensions of the heat s...
The heat sink panel through attachment to the FR-A520-5.5K inverter consist of the top installation frame, bottom installation frame, and upper cover. The to... More Details >>
Heat generation quantity of FR-A500
The heat generation quantity of the FR-A520-5.5K is 310 W. (Reference: The heat generation quantity of the FR-A220E-5.5K is 330 W.) For other capacities, ref... More Details >>
Although you specify the FR-V200 and others as the inverter models, CC-Link is currently supported by the FR-A500 and FR-E500. The FR-V200E does not support ... More Details >>
Motor heat generation at low-speed op...
When using the FR-A540-3.7K in Advanced magnetic flux vector control, operating the motor continuously under the 100% torque at up to 3 Hz does not cause a h... More Details >>
If you connect two frequency setting potentiometers to the terminals 5 and 10, the permissible current of 10 mA is exceeded, and you need to install 2 KΩ res... More Details >>
Controlling multiple VVVFs via commun...
To control multiple inverters using arbitrary signals (4 to 20 mA) simultaneously, it is recommended to connect the signals (4 to 20 mA) in series. (This doe... More Details >>
1. The inverter display is based on the frequency, and the speed and moving speed are displayed by converting the frequency into the corresponding value. The... More Details >>
Current value on input side and outpu...
1. When slight imbalance (approximately 5%) is present with the inverter power supply voltage, the inverter input current can get imbalanced significantly. I... More Details >>