FAQ


FAQAbout Products

- FAQ > Drive Products > Inverters-FREQROL > FREQROL-A500
FAQ
Keyword Search
FREQROL-A500
FAQ within [ FREQROL-A500 ]
-
Two-rank up maximum short-time torque
It is not possible to generate torque larger than the maximum possible torque of the motor by increasing the inverter's capacity.Even when the inverter is up... More Details >>
- No:22027
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Since the terminal FM is designed with 8 V peak pulse voltage output, it cannot output 10 V.Since the terminal AM is an analog output of 0 V to 10 V, use thi... More Details >>
- No:21978
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Change Pr.18 (High speed maximum frequency) to 400 Hz.If you are using the analog command to set the frequency, calibrate the 400 Hz frequency with Pr.903. More Details >>
- No:21931
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
This error is displayed when the inverter and operation panel FR-PU04 cannot communicate with each other correctly or the reset signal remains ON. Therefore,... More Details >>
- No:21546
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Operation of automatic restart after instantaneous power failure
1. No operation log is recorded.2. No. However, you can create a state indicating that automatic restart after instantaneous power failure is in progress by ... More Details >>
- No:21948
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Heat generation quantity of FR-A500
The heat generation quantity of the FR-A520-5.5K is 310 W. (Reference: The heat generation quantity of the FR-A220E-5.5K is 330 W.) For other capacities, ref... More Details >>
- No:21515
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Check if the communication setting parameters (Pr.117 to Pr.124) are set to the same values between the inverter and personal computer.Note that communicatio... More Details >>
- No:22105
- Release Date:2018/08/22 16:31
- Category: Inverters-FREQROL , FREQROL-A500
-
Pulse train output of terminal FM
Under Advanced magnetic flux vector control, the output frequency varies due to slip compensation. This may cause the output frequency monitor value to chang... More Details >>
- No:22054
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
1. You can implement stop-on-contact.2. When implementing stop-on-contact, use the inverter to decelerate the motors to reduce the impact upon stop-on-contac... More Details >>
- No:22041
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
I want to display the speed on an analog meter.
As the inverter does not display the speed in m/min, let us explain using the speed display in r/min. In this case, set Pr.52 to "6" (operation panel display... More Details >>
- No:21944
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
81-90 of Total 123