1. The inverter display is based on the frequency, and the speed and moving speed are displayed by converting the frequency into the corresponding value. The... More Details >>
- No:21480
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Countermeasure against the fault occurrence
When a CC-Link communication fault occurs, the option error (OP3) occurs on the inverter and the output is shut off, and the motor starts coasting. When usin... More Details >>
- No:21531
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
They are capable of a load of 5 VDC±5% and 10 mA. More Details >>
- No:21977
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Inverter installation interchange attachment
Use the FR-A5AT02 as the intercompatibility attachment when upgrading from the FR-A220-3.7K to FR-A540-3.7K. More Details >>
- No:22095
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
When the inverter output shutoff signal MRS is turned on, the output is shut off immediately without regard to setting of Pr.250. More Details >>
- No:21423
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Outgoing harmonic current (0.1 kW, 0.2 kW)
200 V, 0.1 kW to 3.7 kW products are subject to regulation by the harmonic suppression guidelines for household appliances and general-purpose products. Ther... More Details >>
- No:21444
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
There is a 10 ms delay after the inverter recognizes the start command (STF OR STR) before it starts decelerating. The delay is 10 ms. A delay of 100 ms is i... More Details >>
- No:21445
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Torque characteristic at low speed
Torque is not guaranteed for slower than 0.5 Hz. Therefore, no data for this is published. Also, no torque is generated at 0 Hz. More Details >>
- No:21543
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Change Pr.18 (High speed maximum frequency) to 400 Hz.If you are using the analog command to set the frequency, calibrate the 400 Hz frequency with Pr.903. More Details >>
- No:21931
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
You cannot disable the error display. The OC1 overcurrent alarm is displayed. The condition to display this alarm is that the main circuit power supply is OF... More Details >>