FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F500
FAQ
Keyword Search
FAQ within [ FREQROL-F500 ]
-
Class, instance, and attribute represents different grouping of objects.Comparing object grouping to a mailing address, they can be considered as follows:Sta... More Details >>
- No:21924
- Release Date:2018/08/22 16:30
-
Before you change Pr.7 and Pr.8, you must switch to the PU operation mode. Switch to the PU operation mode and change them. More Details >>
- No:21984
- Release Date:2018/08/22 16:30
-
Frequency does not rise with blower
Our suggestion is to adjust the following parameters:1. Set Pr.14 = 0. If the V/F pattern for variable-torque load (Pr.14 = 1) is used, the current may incre... More Details >>
- No:22060
- Release Date:2018/08/22 16:30
-
Speed control failure due to 20 mA from DC 4
It seems that there is a read error for 20 mA DC inside the inverter.Setting Pr.905 to 50 Hz while 20 mA DC is actually flowing between the terminals 4 and 5... More Details >>
- No:21998
- Release Date:2018/08/22 16:30
-
Power factor improving effect by option
Installing the high power factor converter brings the power factor improving effect of 99% or higher.Therefore, when the high power factor converter is used,... More Details >>
- No:22020
- Release Date:2018/08/22 16:30
-
Automatic overload control of inverter
The inverter has the current limit function. This automatically controls the frequency so that the preset current value may not be exceeded. (Note that the m... More Details >>
- No:21409
- Release Date:2018/08/22 16:27
-
Concurrent monitoring of running frequency, output voltage, and output current
Add an analog output by the FR-A5AY.Monitor the three output; output AM (0 to 5 (10) V) and optional 4 to 20 mA, and 0 to 5 (10) V. More Details >>
- No:21959
- Release Date:2018/08/22 16:30
-
Installation method of AM-5 terminal ammeter
The AM-5 output is 0 to 10 VDC voltage output.Therefore, you need to install a voltmeter.Also, since the inverter output current is displayed, the scale of t... More Details >>
- No:22016
- Release Date:2018/08/22 16:30
-
1. By setting Pr.158 (Terminal AM function selection) to "21" (Reference voltage output), 10 V is output from the terminal AM.2. Read Pr.901 in the PU operat... More Details >>
- No:21936
- Release Date:2018/08/22 16:30
-
Using the inverter's input terminal, you can use up to 15 speeds.This function is supported by the current 500 series products (A500, F500, E500, and S500).U... More Details >>
- No:21947
- Release Date:2018/08/22 16:30
1-10 of Total 15