  • Parameter setting

    Yes. The single-phase 200 V can be input. If the single-phase input is performed when Pr.872 (Input phase loss protection) is set to "1", the input phase los... More Details >>

    • No:21270
    • Release Date:2018/08/22 16:26
  • Frequency setting

    You can connect up to three inverters to a single external frequency setting potentiometer to control them.   More Details >>

    • No:21917
    • Release Date:2018/08/22 16:30
  • Frequency

    It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>

    • No:21785
    • Release Date:2018/08/22 16:29
  • Applied terminal

    As described in the instruction manual, use the shielded cable or twisted cable to avoid the influence of noises. More Details >>

    • No:21344
    • Release Date:2018/08/22 16:27
  • Brake resistor

    Use two resistors for the high-duty brake resistor FR-ABR-15K. (Connect two resistors of 18 ? in parallel.) More Details >>

    • No:21329
    • Release Date:2018/08/22 16:27
  • FR-PA07

    Since the multi-speed is given a higher priority, the setting by the setting dial is not enabled unless all of the multi-speed signals are OFF. More Details >>

    • No:21302
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • Terminal FM

    No. This is because the current cannot flow if the total internal impedance of the meter connected to the terminal FM is 300 Ω or higher.You can connect mult... More Details >>

    • No:21864
    • Release Date:2018/08/22 16:29
  • CC-Link

    Yes. However, write the setting data to the RAM of the inverter.Set RWw1 in the setting value and turn ON the frequency setting command RYD.To continuously s... More Details >>

    • No:21825
    • Release Date:2018/08/22 16:29
  • Start command

    Set Pr.338 (Communication command source) to "0" to give a start command from "NET". Set Pr.339 (Speed command source) to "1" to make a frequency setting fro... More Details >>

    • No:21285
    • Release Date:2018/08/22 16:26