FAQ within [ FREQROL-F700P ]

91-100 of Total 294

prev 10 / 30page next
  • Frequency command

    Since the initial value of Pr.13 (Starting frequency) is 0.5 Hz, the operation does not start unless 0.5 Hz or higher frequency is set. When 0.49 Hz is set i... More Details >>

    • No:21251
    • Release Date:2018/08/22 16:26
  • Frequency setting

    You can change the terminal 4 to voltage input. (The terminal 4 is set to the current input terminal at the initial setting.)To change the terminal 4 to volt... More Details >>

    • No:21787
    • Release Date:2018/08/22 16:29
  • Operation method

    Set Pr.79 (Operation mode) to "3" and Pr.161 (Frequency setting/key lock operation selection) to "1". More Details >>

    • No:21249
    • Release Date:2018/08/22 16:26
  • FR-PU04

    While the FR-PU04 does not display parameter names, it displays parameter numbers and you can set them. More Details >>

    • No:21919
    • Release Date:2018/08/22 16:30
  • Switching between PU and NET operation modes

    Set Pr.340 (Communication startup mode selection) to "10".The operation mode can be switched between PU and NET by assigning X65 (PU-NET operation switching)... More Details >>

    • No:21878
    • Release Date:2018/08/22 16:29
  • Output current value

    The detection level of the output current value cannot be changed using a potentiometer or a similar device.   More Details >>

    • No:21779
    • Release Date:2018/08/22 16:29
  • Terminal

    Signals input from the terminal 4 are not enabled if the terminal AU is not ON. For an inverter without the terminal AU, assign the AU function to an unused ... More Details >>

    • No:21679
    • Release Date:2018/08/22 16:28
  • Multi-speed setting

    Priorities are: Low speed (RL) > Middle speed (RM) > High speed (RH).For example, if the low speed (RL) and middle speed (RM) signals are input simulta... More Details >>

    • No:21772
    • Release Date:2018/08/22 16:29
  • Monitor indicator

    No. You cannot check the accumulated number of rotations on the monitor.   More Details >>

    • No:21715
    • Release Date:2018/08/22 16:29
  • PU operation

    The relationship between the acceleration/deceleration reference frequency and acceleration/deceleration time does not change between the PU operation and ex... More Details >>

    • No:21694
    • Release Date:2018/08/22 16:28