  • Running frequency setting

    Pr.338 is for the communication operation command source at communication operation and specifies the command source to supply the start signal.Pr.339 is for... More Details >>

    • No:21880
    • Release Date:2018/08/22 16:29
  • Operation mode setting

    To enable the frequency setting with the setting dial and multi-speed setting, set Pr.79 to "3". Note that multi-speed setting is prioritized over setting us... More Details >>

    • No:21852
    • Release Date:2018/08/22 16:29
  • Display unit of operation panel

    Set the rotations per minute that is obtained while operating at the frequency set with Pr.505 (Speed setting reference) to Pr.37 (Speed display).For example... More Details >>

    • No:21774
    • Release Date:2018/08/22 16:29
  • CC-Link station number setting

    Change the setting in the PU operation mode.   More Details >>

    • No:21747
    • Release Date:2018/08/22 16:29
  • Frequency setting

    This parameter cannot be changed in the external operation mode.Change Pr.77 (Parameter write selection) to "2" before changing the setting of Pr.72. More Details >>

    • No:21743
    • Release Date:2018/08/22 16:29
  • Speed setting

    Use the inverter's calibration parameters Pr.C2/C3, Pr.125/C4 to adjust the bias and gain for each inverter.Connect the wires from the frequency setting pote... More Details >>

    • No:21728
    • Release Date:2018/08/22 16:29
  • Output frequency

    For the FR-E700, only the terminal FM allows for variable output and the output is a pulse signal. Therefore, it cannot be directly input to the programmable... More Details >>

    • No:21682
    • Release Date:2018/08/22 16:28
  • Running frequency

    There are two methods to reduce the running frequency variation. 1. Increase the setting value of Pr.74 (Input filter time constant) to reduce the variation.... More Details >>

    • No:21296
    • Release Date:2018/08/22 16:26
  • Automatic restart after instantaneous power failure

    The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>

    • No:21255
    • Release Date:2018/08/22 16:26
  • Electronic bypass function

    Turn ON and OFF the RES signal to enable the inverter-driven operation. More Details >>

    • No:21190
    • Release Date:2018/08/22 16:26