  • PU operation

    Set Pr.79 (Operation mode) to "1" (PU operation mode) and change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode).   More Details >>

    • No:21863
    • Release Date:2018/08/22 16:29
  • Output voltage

    Since the output frequency was measured, it is considered that the start signal was input correctly.Check the output voltage on the voltage monitor of the in... More Details >>

    • No:21780
    • Release Date:2018/08/22 16:29
  • Saving parameter with FR-Configurator

    When FR Configurator (FR-SW3-SETUP-WJ) is saved as a file from the menu, the extension is "me3". The size of this fie will be large since device settings and... More Details >>

    • No:21311
    • Release Date:2018/08/22 16:26
  • Frequency setting

    You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>

    • No:21915
    • Release Date:2018/08/22 16:30
  • Frequency setting

    Use Pr.125 (Terminal 2 frequency setting gain frequency).  More Details >>

    • No:21913
    • Release Date:2018/08/22 16:30
  • Terminal

    Change Pr.126 (Terminal 4 frequency setting gain frequency). More Details >>

    • No:21677
    • Release Date:2018/08/22 16:28
  • Replacement

    It is Pr.125 (Terminal 2 frequency setting gain frequency). Adjust the slope with C4 (903) (Terminal 2 frequency setting gain) as necessary. More Details >>

    • No:21247
    • Release Date:2018/08/22 16:26
  • Frequency meter

    First, check if Pr.55 (Frequency monitor reference) that is the reference for the FM output is set correctly.Next, operate the inverter (without connecting a... More Details >>

    • No:21808
    • Release Date:2018/08/22 16:29
  • Output frequency

    In the initial setting, it is set to 120 Hz. More Details >>

    • No:21345
    • Release Date:2018/08/22 16:27
  • Frequency setting

    The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current signa... More Details >>

    • No:21800
    • Release Date:2018/08/22 16:29