  • Wiring the terminal

    There is no problem with the wiring. Keep the rating (24 VDC, 0.1 A) of the terminal PC. More Details >>

    • No:21342
    • Release Date:2018/08/22 16:27
  • Input phase loss

    Check if the input side voltage is equally applied to all three phases. The S phase voltage may be low because the input current flows when the voltage of th... More Details >>

    • No:21340
    • Release Date:2018/08/22 16:27
  • CC-Link

    It is OK if stations are set as reserved. More Details >>

    • No:21868
    • Release Date:2018/08/22 16:29
  • Frequency setting

    The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current signa... More Details >>

    • No:21800
    • Release Date:2018/08/22 16:29
  • Reverse rotation prevention selection

    Yes, it does. When the inverter is coasting in the reverse direction, it starts in the reverse direction and switches to the forward rotation after a deceler... More Details >>

    • No:21125
    • Release Date:2018/08/22 16:26
  • Multi-speed setting

    If Pr 27 is not set, the operation starts at the speed of RL. More Details >>

    • No:21123
    • Release Date:2018/08/22 16:26
  • FR-PU04

    While the FR-PU04 does not display parameter names, it displays parameter numbers and you can set them. More Details >>

    • No:21919
    • Release Date:2018/08/22 16:30
  • Terminal setting

    To use the terminal as voltage input, you need to:- Set Pr.267 (Terminal 4 input selection).- Set the voltage/current input switch on the inverter board.- Se... More Details >>

    • No:21771
    • Release Date:2018/08/22 16:29
  • Brake resistor

    Use two resistors for the high-duty brake resistor FR-ABR-15K. (Connect two resistors of 18 ? in parallel.) More Details >>

    • No:21329
    • Release Date:2018/08/22 16:27
  • Fault output terminal A, B, and C

    Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>

    • No:21324
    • Release Date:2018/08/22 16:27