FAQ within [ FREQROL-F700P ]

91-100 of Total 294

prev 10 / 30page next
  • Current setting

    Yes.The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current s... More Details >>

    • No:21770
    • Release Date:2018/08/22 16:29
  • Terminal FM

    No. This is because the current cannot flow if the total internal impedance of the meter connected to the terminal FM is 300 Ω or higher.You can connect mult... More Details >>

    • No:21864
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>

    • No:21788
    • Release Date:2018/08/22 16:29
  • Input phase loss

    The detection time 1 s cannot be changed. More Details >>

    • No:21277
    • Release Date:2018/08/22 16:26
  • Replacement

    It is Pr.125 (Terminal 2 frequency setting gain frequency). Adjust the slope with C4 (903) (Terminal 2 frequency setting gain) as necessary. More Details >>

    • No:21247
    • Release Date:2018/08/22 16:26
  • Monitor indicator

    No. You cannot check the accumulated number of rotations on the monitor.   More Details >>

    • No:21715
    • Release Date:2018/08/22 16:29
  • Brake unit

    The resistors cannot be used in combination other than described. Operations of brake units and inverters are not verified. When resistors are used in uncert... More Details >>

    • No:21328
    • Release Date:2018/08/22 16:27
  • Package

    It is the fixing screw for the inverter cooling fan cover.The size and number of screws depend on the model and capacity.(When exporting the product to the E... More Details >>

    • No:21746
    • Release Date:2018/08/22 16:29
  • Switching between external operation and NET operation

    You can monitor the fault output in both NET operation and external operation. More Details >>

    • No:21686
    • Release Date:2018/08/22 16:28
  • Network operation

    Yes. With the setting "66", you can choose NET operation when X66 is ON, and external operation when X66 is OFF. More Details >>

    • No:21675
    • Release Date:2018/08/22 16:28