  • Frequency setting

    When turning the setting dial to set the frequency, press the "SET" key while the desired value blinks. (The setting frequency and "F" flicker alternately.) More Details >>

    • No:21742
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Pr.1 (Maximum frequency) and Pr.18 (Maximum frequency).   More Details >>

    • No:21744
    • Release Date:2018/08/22 16:29
  • CC-Link

    When configuring the inverter via communication such as CC-Link, some signals still requires to be input from the external terminals.(Terminal OH: External t... More Details >>

    • No:21888
    • Release Date:2018/08/22 16:29
  • CC-Link

    Use Pr.542 to set the station number and Pr.543 to set the baud rate.To set the baud rate to 10 Mbps, set Pr.543 to "4". More Details >>

    • No:21839
    • Release Date:2018/08/22 16:29
  • External terminal

    1. Use the external terminals STF, RL, and SD. (A push-ON switch for operation is required between the terminals STF and SD, and a push-OFF switch is require... More Details >>

    • No:21816
    • Release Date:2018/08/22 16:29
  • Operation mode setting

    To enable the frequency setting with the setting dial and multi-speed setting, set Pr.79 to "3". Note that multi-speed setting is prioritized over setting us... More Details >>

    • No:21852
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>

    • No:21685
    • Release Date:2018/08/22 16:28
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • Terminal FM

    No. This is because the current cannot flow if the total internal impedance of the meter connected to the terminal FM is 300 Ω or higher.You can connect mult... More Details >>

    • No:21864
    • Release Date:2018/08/22 16:29
  • Monitor indicator

    No. You cannot check the accumulated number of rotations on the monitor.   More Details >>

    • No:21715
    • Release Date:2018/08/22 16:29