  • Capacity selection

    Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>

    • No:21326
    • Release Date:2018/08/22 16:27
  • Input phase loss

    The detection time 1 s cannot be changed. More Details >>

    • No:21277
    • Release Date:2018/08/22 16:26
  • Replacement

    It is Pr.125 (Terminal 2 frequency setting gain frequency). Adjust the slope with C4 (903) (Terminal 2 frequency setting gain) as necessary. More Details >>

    • No:21247
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>

    • No:21788
    • Release Date:2018/08/22 16:29
  • Parameter setting

    Set Pr.55 (Frequency monitor reference) to "100 Hz".If the indication of the installed frequency meter does not match the running frequency, use the calibrat... More Details >>

    • No:21768
    • Release Date:2018/08/22 16:29
  • Network operation

    Yes. With the setting "66", you can choose NET operation when X66 is ON, and external operation when X66 is OFF. More Details >>

    • No:21675
    • Release Date:2018/08/22 16:28
  • Parameter setting

    Yes. The single-phase 200 V can be input. If the single-phase input is performed when Pr.872 (Input phase loss protection) is set to "1", the input phase los... More Details >>

    • No:21270
    • Release Date:2018/08/22 16:26
  • Package

    It is the fixing screw for the inverter cooling fan cover.The size and number of screws depend on the model and capacity.(When exporting the product to the E... More Details >>

    • No:21746
    • Release Date:2018/08/22 16:29
  • Multi-speed setting

    Priorities are: Low speed (RL) > Middle speed (RM) > High speed (RH).For example, if the low speed (RL) and middle speed (RM) signals are input simulta... More Details >>

    • No:21772
    • Release Date:2018/08/22 16:29
  • Current setting

    Yes.The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current s... More Details >>

    • No:21770
    • Release Date:2018/08/22 16:29