FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F700P
FAQ
Keyword Search
FAQ within [ FREQROL-F700P ]
-
When turning the setting dial to set the frequency, press the "SET" key while the desired value blinks. (The setting frequency and "F" flicker alternately.) More Details >>
- No:21742
- Release Date:2018/08/22 16:29
-
Electronic thermal O/L relay setting
When using multiple motors, connect an external thermal for each of them. Set Pr.9 to "0" to disable the function. (When multiple motors are present, it is n... More Details >>
- No:21676
- Release Date:2018/08/22 16:28
-
Switching between External operation mode and PU operation mode
Assign X16 signal, and set Pr.79 to "0", to switch the operation mode with turning ON/OFF X16 signal. More Details >>
- No:21288
- Release Date:2018/08/22 16:26
-
Check if the CC-Link wires are short-circuited and/or station numbers are duplicated. More Details >>
- No:21891
- Release Date:2018/08/22 16:29
-
No problem. The inverter actually occupies the reserved bits and does not use them. More Details >>
- No:21890
- Release Date:2018/08/22 16:29
-
Pr.338 is for the communication operation command source at communication operation and specifies the command source to supply the start signal.Pr.339 is for... More Details >>
- No:21880
- Release Date:2018/08/22 16:29
-
Since the operation panels of the E700, D700, and F700PJ do not have keys for the forward (FWD) and reverse (REV) rotations, you can only command rotation in... More Details >>
- No:21841
- Release Date:2018/08/22 16:29
-
For low-speed operation, perform auto tuning and use (Advanced) magnetic flux vector control. More Details >>
- No:21810
- Release Date:2018/08/22 16:29
-
Set Pr.13 (Starting frequency) or Pr.2 (Lower limit) to "5 Hz".Also set Pr.10 (DC injection brake operation frequency) to "5 Hz".The inverter does not operat... More Details >>
- No:21790
- Release Date:2018/08/22 16:29
-
Use the inverter's calibration parameters Pr.C2/C3, Pr.125/C4 to adjust the bias and gain for each inverter.Connect the wires from the frequency setting pote... More Details >>
- No:21728
- Release Date:2018/08/22 16:29