  • Frequency setting

    Even while the inverter is operating, you can use the setting dial to change the frequency and then press the SET key and the inverter operates at the new fr... More Details >>

    • No:21739
    • Release Date:2018/08/22 16:29
  • PU operation

    Set Pr.79 (Operation mode) to "1" (PU operation mode) and change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode).   More Details >>

    • No:21863
    • Release Date:2018/08/22 16:29
  • Adjustment of analog gain

    Use Pr.903 (Frequency setting voltage gain) for setting the FR-E500. For the 700 series, use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (... More Details >>

    • No:21689
    • Release Date:2018/08/22 16:28
  • Installation direction

    Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>

    • No:21286
    • Release Date:2018/08/22 16:26
  • Frequency

    When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>

    • No:21284
    • Release Date:2018/08/22 16:26
  • Operation panel (DU04)

    The FR-DU04 can be used in the 700 series inverters, however, some restrictions apply and parameter copy is disabled. More Details >>

    • No:21261
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • External multi-speed setting and multi-speed command

    It depends on the setting of Pr.79 (Operation mode).Pr.79 can be set to "2" or "3".If Pr.79 is "2", it is judged that the multi-speed frequency command was s... More Details >>

    • No:21815
    • Release Date:2018/08/22 16:29
  • JOG function

    When Pr.79 is set to "3", the JOG operation is not available by turning ON the terminal JOG.Instead of the JOG function, you can set the low-speed RL of the ... More Details >>

    • No:21760
    • Release Date:2018/08/22 16:29
  • Electromagnetic contactor

    Turning ON/OFF the output side during operation causes open/close surges that may trigger the protective function (against overcurrent or overvoltage) of the... More Details >>

    • No:21725
    • Release Date:2018/08/22 16:29