  • Running frequency

    The power supply voltage may have dropped.Read the converter output voltage monitor (Pr.55 = 8) and check if Converter output voltage monitor/√2 is within th... More Details >>

    • No:21820
    • Release Date:2018/08/22 16:29
  • Minimum frequency

    If any other frequency is not set, when the start signal is input, the inverter starts acceleration from 0.5 Hz set with Pr.13 (Starting frequency) up to 3 H... More Details >>

    • No:21777
    • Release Date:2018/08/22 16:29
  • Current setting

    Yes.The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current s... More Details >>

    • No:21770
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You need to press the "SET" key with the initial setting.The frequency is not set unless you press the "SET" key.Setting Pr.161 (Frequency setting/key lock o... More Details >>

    • No:21735
    • Release Date:2018/08/22 16:29
  • Motor coasting

    To set the motor to coasting state, the following methods are available: 1. Set Pr.250 (Stop selection) to "0" and turn OFF the start command. 2. Short the t... More Details >>

    • No:21271
    • Release Date:2018/08/22 16:26
  • Model selection

    Use the FR-A740. Basically, select the capacity according to the calculation result of "rated inverter output current ? rated motor current × 1.1". More Details >>

    • No:21244
    • Release Date:2018/08/22 16:26
  • Wiring length

    The total wiring length is as follows: 100 m + (20 m × 5) = 200m. More Details >>

    • No:21144
    • Release Date:2018/08/22 16:26
  • Multi-speed setting

    If Pr 27 is not set, the operation starts at the speed of RL. More Details >>

    • No:21123
    • Release Date:2018/08/22 16:26
  • External terminal

    1. Use the external terminals STF, RL, and SD. (A push-ON switch for operation is required between the terminals STF and SD, and a push-OFF switch is require... More Details >>

    • No:21816
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Pr.1 (Maximum frequency) and Pr.18 (Maximum frequency).   More Details >>

    • No:21744
    • Release Date:2018/08/22 16:29