  • Output voltage

    Since the output frequency was measured, it is considered that the start signal was input correctly.Check the output voltage on the voltage monitor of the in... More Details >>

    • No:21780
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You can set the running frequency up to 400 Hz.It depends on the specifications of the motor used whether or not operation with a frequency of 120 Hz or high... More Details >>

    • No:21738
    • Release Date:2018/08/22 16:29
  • Frequency

    When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>

    • No:21284
    • Release Date:2018/08/22 16:26
  • Rated frequency setting

    Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>

    • No:21280
    • Release Date:2018/08/22 16:26
  • Motor coasting

    To set the motor to coasting state, the following methods are available: 1. Set Pr.250 (Stop selection) to "0" and turn OFF the start command. 2. Short the t... More Details >>

    • No:21271
    • Release Date:2018/08/22 16:26
  • Frequency setting signal

    Calibrate C6 (Pr.904) (Terminal 4 frequency setting bias frequency) and C7 (Pr.905) (Terminal 4 frequency setting gain frequency). If the situation does not ... More Details >>

    • No:21265
    • Release Date:2018/08/22 16:26
  • Output frequency

    When Pr.80 and Pr.81 are set to the value other than "9999", control other than V/F control is performed. For the FR-F700(P) FR-D700, and FR-F700PJ, Pr.81 is... More Details >>

    • No:21259
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • Frequency setting

    Set Pr.338 (Operation command source) to "1" (external terminal).Set Pr.339 (Speed command source) to "0" (communication).Check the setting of Pr.79 for oper... More Details >>

    • No:21869
    • Release Date:2018/08/22 16:29
  • Fault output terminal A, B, and C

    Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>

    • No:21324
    • Release Date:2018/08/22 16:27