FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F700P
FAQ
Keyword Search
FAQ within [ FREQROL-F700P ]
-
Set Pr.52 (DU/PU main display data selection) to "100".Displaying the setting frequency while the inverter is stopped and the output frequency while it is op... More Details >>
- No:21783
- Release Date:2018/08/22 16:29
-
Switching between external operation and NET operation
You can monitor the fault output in both NET operation and external operation. More Details >>
- No:21686
- Release Date:2018/08/22 16:28
-
Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>
- No:21280
- Release Date:2018/08/22 16:26
-
Yes. More Details >>
- No:21871
- Release Date:2018/08/22 16:29
-
Set Pr.37 (Speed display) to the speed obtained when operating the machine at the frequency set with Pr.505 (Speed setting reference). (For FR-F700/E700/D700... More Details >>
- No:21716
- Release Date:2018/08/22 16:29
-
Set Pr.338 (Communication command source) to "0" to give a start command from "NET". Set Pr.339 (Speed command source) to "1" to make a frequency setting fro... More Details >>
- No:21285
- Release Date:2018/08/22 16:26
-
To set the motor to coasting state, the following methods are available: 1. Set Pr.250 (Stop selection) to "0" and turn OFF the start command. 2. Short the t... More Details >>
- No:21271
- Release Date:2018/08/22 16:26
-
Since Pr.125 (Terminal 2 frequency setting gain frequency) is initially set to 60 Hz, change it to 85 Hz. More Details >>
- No:21907
- Release Date:2018/08/22 16:30
-
Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>
- No:21845
- Release Date:2018/08/22 16:29
-
You need to press the "SET" key with the initial setting.The frequency is not set unless you press the "SET" key.Setting Pr.161 (Frequency setting/key lock o... More Details >>
- No:21735
- Release Date:2018/08/22 16:29
111-120 of Total 294