The output frequency is not changed by the maximum frequency setting. It can be changed by the following methods. - Set the frequency on the operation panel.... More Details >>
- No:21347
- Release Date:2018/08/22 16:27
-
Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>
- No:21280
- Release Date:2018/08/22 16:26
-
Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>
- No:21909
- Release Date:2018/08/22 16:30
-
NET mode, external operation switching
You can switch between the NET mode and external operation.Assign the X66 signal (Operation switching) to an unused terminal for switching.Also, set Pr.79 (O... More Details >>
- No:21906
- Release Date:2018/08/22 16:30
-
Set Pr.52 (DU/PU main display data selection) to "5".This allows for displaying the setting frequency on the voltage monitor.Then, switch to the monitor mode... More Details >>
- No:21784
- Release Date:2018/08/22 16:29
-
Switching between external operation and NET operation
You can monitor the fault output in both NET operation and external operation. More Details >>
- No:21686
- Release Date:2018/08/22 16:28
-
Connecting ammeter to output side
Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>
- No:21681
- Release Date:2018/08/22 16:28
-
As described in the instruction manual, use the shielded cable or twisted cable to avoid the influence of noises. More Details >>
- No:21344
- Release Date:2018/08/22 16:27
-
Calibrate C6 (Pr.904) (Terminal 4 frequency setting bias frequency) and C7 (Pr.905) (Terminal 4 frequency setting gain frequency). If the situation does not ... More Details >>
- No:21265
- Release Date:2018/08/22 16:26
-
Signals input from the terminal 4 are not enabled if the terminal AU is not ON. For an inverter without the terminal AU, assign the AU function to an unused ... More Details >>
- No:21679
- Release Date:2018/08/22 16:28
111-120 of Total 294