Operation mode, PU operation mode switching
Change Pr.340 (Communication startup mode selection) from "1" to "0".Power OFF and then ON the inverter.Operate the inverter according to the value of Pr.79 ... More Details >>
- No:21870
- Release Date:2018/08/22 16:29
-
Connection cable of FR-Configurator
It is the standardized Mini-B connector. More Details >>
- No:21312
- Release Date:2018/08/22 16:26
-
FR-Configurator (FR-SW3-STUP-WJ) is the Japanese version. FR-Configurator (FR-SW3-SETUP-WE) is the English version. More Details >>
- No:21308
- Release Date:2018/08/22 16:26
-
You can connect up to three inverters to a single external frequency setting potentiometer to control them. More Details >>
- No:21917
- Release Date:2018/08/22 16:30
-
Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>
- No:21909
- Release Date:2018/08/22 16:30
-
The detection level of the output current value cannot be changed using a potentiometer or a similar device. More Details >>
- No:21779
- Release Date:2018/08/22 16:29
-
Yes, you can use the setup software (FR-SW3-SETUP-WJ) to set it. More Details >>
- No:21711
- Release Date:2018/08/22 16:29
-
When Pr.80 and Pr.81 are set to the value other than "9999", control other than V/F control is performed. For the FR-F700(P) FR-D700, and FR-F700PJ, Pr.81 is... More Details >>
- No:21259
- Release Date:2018/08/22 16:26
-
Set Pr.56 (Current monitor reference) to "10A". More Details >>
- No:21865
- Release Date:2018/08/22 16:29
-
You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>
- No:21915
- Release Date:2018/08/22 16:30