  • Frequency setting

    Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>

    • No:21788
    • Release Date:2018/08/22 16:29
  • Electromagnetic contactor

    It cannot be avoided by using parameters.   More Details >>

    • No:21724
    • Release Date:2018/08/22 16:29
  • Parameter setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) to "50 Hz".Set Pr.1 (Maximum frequency) to "50 Hz". More Details >>

    • No:21720
    • Release Date:2018/08/22 16:29
  • Terminal FM

    You can connect a 1 mA full scale ammeter with internal resistance 300 Ω or lower. More Details >>

    • No:21680
    • Release Date:2018/08/22 16:28
  • Cooling fan

    Pr.244 (Cooling fan operation selection) controls turning ON/OFF of the cooling fan and is initially set to "1". When the inverter is powered ON, the cooling... More Details >>

    • No:21670
    • Release Date:2018/08/22 16:28
  • Brake resistor

    It will be the shared type. More Details >>

    • No:21331
    • Release Date:2018/08/22 16:27
  • Graph function in FR-Configurator

    Even the USB is used, FR Configurator requires at least 50 ms sampling time (for each monitoring item). In this case, since three types of data are monitored... More Details >>

    • No:21310
    • Release Date:2018/08/22 16:26
  • Number of stations that can be set in FR Configurator

    The station numbers that can be set differ depending on the version of FR-Configurator (FR-SW3-SETUP-WJ) setup software. For Ver.2.00 or later, station numbe... More Details >>

    • No:21305
    • Release Date:2018/08/22 16:26
  • FR-PA07

    Since the FR-PA07 has the back cover and adapter, the FR-E5P is not necessary. More Details >>

    • No:21304
    • Release Date:2018/08/22 16:26
  • Speed command

    Calibrate the terminal 2 bias. More Details >>