The power supply voltage may have dropped.Read the converter output voltage monitor (Pr.55 = 8) and check if Converter output voltage monitor/√2 is within th... More Details >>
- No:21820
- Release Date:2018/08/22 16:29
-
External multi-speed setting and multi-speed command
It depends on the setting of Pr.79 (Operation mode).Pr.79 can be set to "2" or "3".If Pr.79 is "2", it is judged that the multi-speed frequency command was s... More Details >>
- No:21815
- Release Date:2018/08/22 16:29
-
In this case, the JOG operation is prioritized.When the terminals JOG and SD are short-circuited and turned ON, the frequency setting by the external potenti... More Details >>
- No:21804
- Release Date:2018/08/22 16:29
-
You can change the full-scale value by changing Pr.55 (Frequency monitor reference). The initial setting is 60 Hz. More Details >>
- No:21672
- Release Date:2018/08/22 16:28
-
If Pr 27 is not set, the operation starts at the speed of RL. More Details >>
- No:21123
- Release Date:2018/08/22 16:26
-
Yes.The inverter requires the start signal and frequency setting signal. More Details >>
- No:21793
- Release Date:2018/08/22 16:29
-
Yes, you can set Pr.20 to 20 Hz. More Details >>
- No:21683
- Release Date:2018/08/22 16:28
-
It is not switched. The frequency at the fault saved in the faults history is always displayed in frequency [Hz]. More Details >>
- No:21180
- Release Date:2018/08/22 16:26
-
You also need to set Pr.79 (Operation mode) to "3". More Details >>
- No:21844
- Release Date:2018/08/22 16:29
-
The adapter is not necessary. Only the dedicated cable FR-CB20□ is required. More Details >>
- No:21362
- Release Date:2018/08/22 16:27