FAQ within [ FREQROL-F700P ]

151-160 of Total 294

prev 16 / 30page next
  • Terminals P1 and P

    Removal of the jumper between the terminals P1 and P is not necessary unless you are using the DC reactor.Set Pr.30 = "0" when using the brake unit.Since set... More Details >>

    • No:21921
    • Release Date:2018/08/22 16:30
  • Parameter

    Press the "MODE" key on the operation panel several times to display "P.0" and parameter setting screen. Then turn the setting dial to display "C..." screen ... More Details >>

    • No:21336
    • Release Date:2018/08/22 16:27
  • Easy setting mode

    If "HOLD" is displayed, the key lock mode enabled. Press the "MODE" key for two seconds. Then, change the setting of Pr.79 to "1". More Details >>

    • No:21350
    • Release Date:2018/08/22 16:27
  • Network operation

    Set Pr.338 to "0" (NET) and Pr.339 to "1" or "2". More Details >>

    • No:21674
    • Release Date:2018/08/22 16:28
  • Frequency, monitor setting

    Set Pr.52 (PU/DU main display data selection) to "5".Set the monitor as the third monitor, frequency -> current -> setting frequency. More Details >>

    • No:21745
    • Release Date:2018/08/22 16:29
  • Frequency setting

    As the AS-OX has the "0ADJ" potentiometer for frequency meter calibration, use it to adjust the meter so that both readings match.   More Details >>

    • No:21795
    • Release Date:2018/08/22 16:29
  • Frequency setting

    To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>

    • No:21799
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Normally, any of the PU, EXT, or NET LED turns ON.Check if the parameter unit FR-PU04/FR-PU07 or operation panel FR-PA07 is externally connected to the PU co... More Details >>

    • No:21803
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • Electronic bypass function

    The operation cannot be manually switched to the commercial power supply operation at an inverter fault. The operation can be automatically switched to the c... More Details >>

    • No:21191
    • Release Date:2018/08/22 16:26