  • Applied terminal

    As described in the instruction manual, use the shielded cable or twisted cable to avoid the influence of noises. More Details >>

    • No:21344
    • Release Date:2018/08/22 16:27
  • FR-Configurator

    Yes, you can use the setup software (FR-SW3-SETUP-WJ) to set it.   More Details >>

    • No:21711
    • Release Date:2018/08/22 16:29
  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29
  • Frequency setting

    From the LED, it is considered that the operation mode Pr.79 is set to "3".The PU and EXT LEDs turn ON with this setting.In this state, you cannot change bet... More Details >>

    • No:21741
    • Release Date:2018/08/22 16:29
  • Frequency setting

    This parameter cannot be changed in the external operation mode.Change Pr.77 (Parameter write selection) to "2" before changing the setting of Pr.72. More Details >>

    • No:21743
    • Release Date:2018/08/22 16:29
  • Frequency

    It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>

    • No:21785
    • Release Date:2018/08/22 16:29
  • Transistor output module of the programmable controller

    Check if signals that are ON when the programmable controller's transistor output starts are always ON. More Details >>

    • No:21811
    • Release Date:2018/08/22 16:29
  • Setting dial

    Yes. You can use the setting dial of the inverter to set the frequency as well as change the parameter values. More Details >>

    • No:21846
    • Release Date:2018/08/22 16:29
  • Multi-speed setting

    If Pr 27 is not set, the operation starts at the speed of RL. More Details >>

    • No:21123
    • Release Date:2018/08/22 16:26
  • Rotation speed display

    It is not switched. The frequency at the fault saved in the faults history is always displayed in frequency [Hz]. More Details >>

    • No:21180
    • Release Date:2018/08/22 16:26