FAQ within [ FREQROL-F700P ]

181-190 of Total 295

prev 19 / 30page next
  • External terminal

    1. Use the external terminals STF, RL, and SD. (A push-ON switch for operation is required between the terminals STF and SD, and a push-OFF switch is require... More Details >>

    • No:21816
    • Release Date:2018/08/22 16:29
  • Setting dial

    Yes. You can use the setting dial of the inverter to set the frequency as well as change the parameter values. More Details >>

    • No:21846
    • Release Date:2018/08/22 16:29
  • NET mode, external operation switching

    You can switch between the NET mode and external operation.Assign the X66 signal (Operation switching) to an unused terminal for switching.Also, set Pr.79 (O... More Details >>

    • No:21906
    • Release Date:2018/08/22 16:30
  • Frequency setting

    You can use it for inverter operation, but the running speed of the inverter does not change linearly with regard to turn of the frequency setting potentiome... More Details >>

    • No:21912
    • Release Date:2018/08/22 16:30
  • Multi-speed setting

    If Pr 27 is not set, the operation starts at the speed of RL. More Details >>

    • No:21123
    • Release Date:2018/08/22 16:26
  • Proportional band of multiple inverters

    By importing the operation frequency from the AM terminal (analog output) of the first inverter to the FR-FH (ratio setter), the operation command which is p... More Details >>

    • No:21250
    • Release Date:2018/08/22 16:26
  • Frequency command

    Since the initial value of Pr.13 (Starting frequency) is 0.5 Hz, the operation does not start unless 0.5 Hz or higher frequency is set. When 0.49 Hz is set i... More Details >>

    • No:21251
    • Release Date:2018/08/22 16:26
  • Output frequency

    When Pr.80 and Pr.81 are set to the value other than "9999", control other than V/F control is performed. For the FR-F700(P) FR-D700, and FR-F700PJ, Pr.81 is... More Details >>

    • No:21259
    • Release Date:2018/08/22 16:26
  • Frequency setting signal

    Set C5 (Pr.904) (Terminal 4 frequency setting bias frequency) to 0 Hz and Pr.126 (Terminal 4 frequency setting gain frequency) to 50 Hz. More Details >>

    • No:21268
    • Release Date:2018/08/22 16:26
  • Installation direction

    Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>

    • No:21286
    • Release Date:2018/08/22 16:26

181-190 of Total 295