No, we have no cable 50 cm long. The optional cables 1 m, 3 m, and 5 m long are available. (1 m: FR-CB201, 3 m: FR-CB203, 5 m: FR-CB205) More Details >>
- No:21365
- Release Date:2018/08/22 16:27
-
Pr.1 (Maximum frequency) and Pr.18 (Maximum frequency). More Details >>
- No:21744
- Release Date:2018/08/22 16:29
-
After setting Pr.340 to "10", you need to power OFF then ON the inverter to make the new setting enabled because you are setting the operation upon power-on.... More Details >>
- No:21759
- Release Date:2018/08/22 16:29
-
Set Pr.55 (Frequency monitor reference) to "100 Hz".If the indication of the installed frequency meter does not match the running frequency, use the calibrat... More Details >>
- No:21768
- Release Date:2018/08/22 16:29
-
Calibrate the terminal 2 bias. More Details >>
- No:21281
- Release Date:2018/08/22 16:26
-
Supported model for FR-Configurator
The FR-E700 is not supported by FR-SW2-SETUP-WJ. The FR-E700 series are supported by FR-SW3-SETUP-WJ. This software can be downloaded from the Mitsubishi Ele... More Details >>
- No:21314
- Release Date:2018/08/22 16:26
-
Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>
- No:21326
- Release Date:2018/08/22 16:27
-
Check if the input side voltage is equally applied to all three phases. The S phase voltage may be low because the input current flows when the voltage of th... More Details >>
- No:21340
- Release Date:2018/08/22 16:27
-
The forward rotation and reverse rotation are enabled by pressing the FWD/REV key on the operation panel. More Details >>
- No:21364
- Release Date:2018/08/22 16:27
-
Signals input from the terminal 4 are not enabled if the terminal AU is not ON. For an inverter without the terminal AU, assign the AU function to an unused ... More Details >>
- No:21679
- Release Date:2018/08/22 16:28