- No:21874
- Release Date:2018/08/22 16:29
-
Connect the wire to the optional FR-A7NC's terminal block. (The terminal block is detachable.) More Details >>
- No:21875
- Release Date:2018/08/22 16:29
-
Switching between PU and NET operation modes
Set Pr.340 (Communication startup mode selection) to "10".The operation mode can be switched between PU and NET by assigning X65 (PU-NET operation switching)... More Details >>
- No:21878
- Release Date:2018/08/22 16:29
-
You can use it with the 700 series inverters. Note that the installation method of the card differs for the FR-E700 series and FR-A700/F700 series.If you hav... More Details >>
- No:21887
- Release Date:2018/08/22 16:29
-
Check if the CC-Link wires are short-circuited and/or station numbers are duplicated. More Details >>
- No:21891
- Release Date:2018/08/22 16:29
-
Since Pr.125 (Terminal 2 frequency setting gain frequency) is initially set to 60 Hz, change it to 85 Hz. More Details >>
- No:21907
- Release Date:2018/08/22 16:30
-
You can use it for inverter operation, but the running speed of the inverter does not change linearly with regard to turn of the frequency setting potentiome... More Details >>
- No:21912
- Release Date:2018/08/22 16:30
-
You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>
- No:21915
- Release Date:2018/08/22 16:30
-
Pr.30 = "1" and Pr.70 = "0". More Details >>
- No:21143
- Release Date:2018/08/22 16:26
-
To set the motor to coasting state, the following methods are available: 1. Set Pr.250 (Stop selection) to "0" and turn OFF the start command. 2. Short the t... More Details >>
- No:21271