  • Replacement

    The station number and baud rate were set using the dial for the FR-A5NC, but parameter is used for the FR-A7NC. Pr.542 (Communication station number (CC-Lin... More Details >>

    • No:21248
    • Release Date:2018/08/22 16:26
  • 4 to 20 mA output

    Yes. It is available by using the FR-A7AY (plug-in option). By setting Pr.307 (Setting for zero analog output) to "20" and Pr.309 (Analog output signal volta... More Details >>

    • No:21246
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Since Pr.125 (Terminal 2 frequency setting gain frequency) is initially set to 60 Hz, change it to 85 Hz. More Details >>

    • No:21907
    • Release Date:2018/08/22 16:30
  • Frequency setting

    For the set frequency 60 Hz, ±6 Hz is applied and thus the up to frequency signal is output between 54 Hz and 66 Hz. During acceleration/deceleration to the ... More Details >>

    • No:21348
    • Release Date:2018/08/22 16:27
  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29
  • FR-PA07

    Operations cannot be enabled separately. You only can disable or enable all the operations. More Details >>

    • No:21366
    • Release Date:2018/08/22 16:27
  • Printing files saved in the previous version of FR-Configurator

    The parameter file of FR-SW3 cannot be printed using FR-SW2. The latest version of FR-SW3 can be downloaded from the Mitsubishi Electric FA Global Website. U... More Details >>

    • No:21315
    • Release Date:2018/08/22 16:27
  • CC-Link

    It is OK if stations are set as reserved. More Details >>

    • No:21868
    • Release Date:2018/08/22 16:29
  • CC-Link

    To set the frequency via CC-Link communication, the NET mode should be selected. The new parameter setting is applied after powering OFF and then ON the inve... More Details >>

    • No:21763
    • Release Date:2018/08/22 16:29
  • Programmable controller

    The error LED on the master side of the programmable controller blinks (faulty station present).According to the SW80 station information, an error flag is a... More Details >>

    • No:21813
    • Release Date:2018/08/22 16:29