  • Frequency setting

    Since the percent value read by the calibration parameter C7 indicates that the voltage of 10 V is internally detected as 101.0%, use 101.0% as is.If you cha... More Details >>

    • No:21740
    • Release Date:2018/08/22 16:29
  • Saving parameter with FR-Configurator

    When FR Configurator (FR-SW3-SETUP-WJ) is saved as a file from the menu, the extension is "me3". The size of this fie will be large since device settings and... More Details >>

    • No:21311
    • Release Date:2018/08/22 16:26
  • CC-Link

    You can select from the output power (in 0.01 kW units) and cumulative energy (in 1 kWh/0.01 kWh units). More Details >>

    • No:21885
    • Release Date:2018/08/22 16:29
  • CC-Link communication

    After setting Pr.79 (Operation mode selection) to "2" and Pr.340 (Communication startup mode selection) to "10", reset the inverter (or power ON again) to st... More Details >>

    • No:21256
    • Release Date:2018/08/22 16:26
  • CC-Link

    The way to monitor the output current and read parameters via CC-Link is identical in all operation modes.  More Details >>

    • No:21872
    • Release Date:2018/08/22 16:29
  • Programmable controller

    Please use the inverter optional FR-A7AY.It supports voltage output (0 to 10 VDC) and current output (0 to 20 mA DC).For the voltage output (0 to 10 VDC), th... More Details >>

    • No:21812
    • Release Date:2018/08/22 16:29
  • Frequency meter

    First, check if Pr.55 (Frequency monitor reference) that is the reference for the FM output is set correctly.Next, operate the inverter (without connecting a... More Details >>

    • No:21808
    • Release Date:2018/08/22 16:29
  • Frequency setting

    To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>

    • No:21799
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You cannot calibrate the frequency around the middle of the current input range.The inverter determines the top and bottom points in the bias/gain adjustment... More Details >>

    • No:21736
    • Release Date:2018/08/22 16:29
  • Electromagnetic contactor

    Turning ON/OFF the output side during operation causes open/close surges that may trigger the protective function (against overcurrent or overvoltage) of the... More Details >>

    • No:21725
    • Release Date:2018/08/22 16:29