Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>
- No:21788
- Release Date:2018/08/22 16:29
-
External installationRated current
Since the external thermal prevents the motor from being overheated, install it between the output terminal of the inverter and the motor.The rated current i... More Details >>
- No:21817
- Release Date:2018/08/22 16:29
-
Set Pr.79 (Operation mode) to "1" (PU operation mode) and change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode). More Details >>
- No:21863
- Release Date:2018/08/22 16:29
-
When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>
- No:21284
- Release Date:2018/08/22 16:26
-
As described in the instruction manual, use the shielded cable or twisted cable to avoid the influence of noises. More Details >>
- No:21344
- Release Date:2018/08/22 16:27
-
FR-Configurator (FR-SW3-STUP-WJ) is the Japanese version. FR-Configurator (FR-SW3-SETUP-WE) is the English version. More Details >>
- No:21308
- Release Date:2018/08/22 16:26
-
Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>
- No:21685
- Release Date:2018/08/22 16:28
-
It is not stored in a parameter but memorized as the frequency setting value after acceleration by the acceleration signal.You can also choose whether or not... More Details >>
- No:21733
- Release Date:2018/08/22 16:29
-
Press the "SET" key once while the output frequency is monitored.The unit indicator LED changes from "Hz" to "A" and the monitor display changes to the current. More Details >>
- No:21764
- Release Date:2018/08/22 16:29
-
The calibration parameter C6 (Terminal 4 frequency setting bias) is initially set to "20%". Therefore, voltage input to the terminal 4 does not become effect... More Details >>
- No:21806
- Release Date:2018/08/22 16:29