  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) instead of Pr.1 (Maximum frequency).   More Details >>

    • No:21802
    • Release Date:2018/08/22 16:29
  • Frequency setting

    To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>

    • No:21799
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Yes, you can set them randomly.   More Details >>

    • No:21796
    • Release Date:2018/08/22 16:29
  • Frequency setting

    When the potentiometer is disconnected and frequency commands cease, the input potential becomes around 0 V.Therefore, the frequency command becomes analog-c... More Details >>

    • No:21794
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You can use the setting dial to set the frequency during operation even if Pr.77 is not set to "2".Setting Pr.77 to "2" allows for changing the parameter set... More Details >>

    • No:21786
    • Release Date:2018/08/22 16:29
  • Frequency

    It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>

    • No:21785
    • Release Date:2018/08/22 16:29
  • Setting frequency

    Set Pr.52 (DU/PU main display data selection) to "100".Displaying the setting frequency while the inverter is stopped and the output frequency while it is op... More Details >>

    • No:21783
    • Release Date:2018/08/22 16:29
  • Terminal setting

    To use the terminal as voltage input, you need to:- Set Pr.267 (Terminal 4 input selection).- Set the voltage/current input switch on the inverter board.- Se... More Details >>

    • No:21771
    • Release Date:2018/08/22 16:29
  • Parameter

    No parameter can be used to directly set this time.Changing Pr.9 (Electronic thermal O/L relay) changes the time. More Details >>

    • No:21769
    • Release Date:2018/08/22 16:29
  • PU operation

    The relationship between the acceleration/deceleration reference frequency and acceleration/deceleration time does not change between the PU operation and ex... More Details >>

    • No:21694
    • Release Date:2018/08/22 16:28