FAQ within [ FREQROL-F700P ]

221-230 of Total 294

prev 23 / 30page next
  • Electronic bypass function

    With the automatic bypass sequence (Pr.139 ≠ 9999, Pr.159 = 9999), the motor operation is switched to commercial power supply operation when the output frequ... More Details >>

    • No:21189
    • Release Date:2018/08/22 16:26
  • CC-Link

    Yes. However, write the setting data to the RAM of the inverter.Set RWw1 in the setting value and turn ON the frequency setting command RYD.To continuously s... More Details >>

    • No:21825
    • Release Date:2018/08/22 16:29
  • Frequency setting

    As the AS-OX has the "0ADJ" potentiometer for frequency meter calibration, use it to adjust the meter so that both readings match.   More Details >>

    • No:21795
    • Release Date:2018/08/22 16:29
  • Minimum frequency

    If any other frequency is not set, when the start signal is input, the inverter starts acceleration from 0.5 Hz set with Pr.13 (Starting frequency) up to 3 H... More Details >>

    • No:21777
    • Release Date:2018/08/22 16:29
  • Output frequency

    For the FR-E700, only the terminal FM allows for variable output and the output is a pulse signal. Therefore, it cannot be directly input to the programmable... More Details >>

    • No:21682
    • Release Date:2018/08/22 16:28
  • CC-Link

    No problem. The inverter actually occupies the reserved bits and does not use them. More Details >>

    • No:21890
    • Release Date:2018/08/22 16:29
  • External installationRated current

    Since the external thermal prevents the motor from being overheated, install it between the output terminal of the inverter and the motor.The rated current i... More Details >>

    • No:21817
    • Release Date:2018/08/22 16:29
  • CC-Link

    To set the frequency via CC-Link communication, the NET mode should be selected. The new parameter setting is applied after powering OFF and then ON the inve... More Details >>

    • No:21763
    • Release Date:2018/08/22 16:29
  • Terminal indicator lamp

    The inverter outputs the peak voltage 300 to 400 VDC of the bus voltage not in a pure sine wave but a in a PWM waveform. Check if the lamp to be connected ca... More Details >>

    • No:21323
    • Release Date:2018/08/22 16:27
  • Electronic bypass function

    No, it is not available. It is only available in the External operation mode or combined operation mode (PU speed command and External operation command (Pr.... More Details >>

    • No:21192
    • Release Date:2018/08/22 16:26