The relationship between the acceleration/deceleration reference frequency and acceleration/deceleration time does not change between the PU operation and ex... More Details >>
- No:21694
- Release Date:2018/08/22 16:28
-
Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>
- No:21685
- Release Date:2018/08/22 16:28
-
Operations cannot be enabled separately. You only can disable or enable all the operations. More Details >>
- No:21366
- Release Date:2018/08/22 16:27
-
1. Yes. 2. Set Pr.17 to "2". 3. If the start signal is ON, the operation continues even the emergency stop is OFF. More Details >>
- No:21359
- Release Date:2018/08/22 16:27
-
When Pr.79 is set to "3", since the start command is in the External operation mode, the RUN key of FR-PA07 does not work. More Details >>
- No:21303
- Release Date:2018/08/22 16:26
-
Calibrate the terminal 2 bias. More Details >>
- No:21281
- Release Date:2018/08/22 16:26
-
No, it is not available. It is only available in the External operation mode or combined operation mode (PU speed command and External operation command (Pr.... More Details >>
- No:21192
- Release Date:2018/08/22 16:26
-
The total wiring length is as follows: 100 m + (20 m × 5) = 200m. More Details >>
- No:21144
- Release Date:2018/08/22 16:26
-
"n" in the address RWwn indicates a value determined by the station number setting. More Details >>
- No:21867
- Release Date:2018/08/22 16:29
-
Turn ON the monitor command RYC. More Details >>
- No:21826
- Release Date:2018/08/22 16:29