10 VDC voltage from terminal 10
Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>
- No:21727
- Release Date:2018/08/22 16:29
-
1. Set Pr.162 to "10" (Frequency search at every start).2. You can ignore the setting if the motor excitation current is unknown. More Details >>
- No:21718
- Release Date:2018/08/22 16:29
-
Connecting ammeter to output side
Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>
- No:21681
- Release Date:2018/08/22 16:28
-
Signals input from the terminal 4 are not enabled if the terminal AU is not ON. For an inverter without the terminal AU, assign the AU function to an unused ... More Details >>
- No:21679
- Release Date:2018/08/22 16:28
-
No, we have no cable 50 cm long. The optional cables 1 m, 3 m, and 5 m long are available. (1 m: FR-CB201, 3 m: FR-CB203, 5 m: FR-CB205) More Details >>
- No:21365
- Release Date:2018/08/22 16:27
-
Specific settings are not required, however, when replacing the FR-E500, check that Pr.146 (Built-in potentiometer switchover) is not set to "0". If it is "0... More Details >>
- No:21363
- Release Date:2018/08/22 16:27
-
If "HOLD" is displayed, the key lock mode enabled. Press the "MODE" key for two seconds. Then, change the setting of Pr.79 to "1". More Details >>
- No:21350
- Release Date:2018/08/22 16:27
-
Saving parameter with FR-Configurator
When FR Configurator (FR-SW3-SETUP-WJ) is saved as a file from the menu, the extension is "me3". The size of this fie will be large since device settings and... More Details >>
- No:21311
- Release Date:2018/08/22 16:26
-
Set Pr.55 (Frequency monitoring reference) of the first inverter to 70 Hz. More Details >>
- No:21257
- Release Date:2018/08/22 16:26
-
The operation cannot be manually switched to the commercial power supply operation at an inverter fault. The operation can be automatically switched to the c... More Details >>
- No:21191
- Release Date:2018/08/22 16:26