FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F700P
FAQ
Keyword Search
FAQ within [ FREQROL-F700P ]
-
Yes. More Details >>
- No:21713
- Release Date:2018/08/22 16:29
-
Model setting in FR-Configurator
Check the version of FR-Configurator (FR-SW3-SETUP-WJ). If the version is "1.00", it does not support or detect the FR-E740. Version "2.00" supports the FR-E... More Details >>
- No:21309
- Release Date:2018/08/22 16:26
-
Yes.You can issue operation (forward/reverse), frequency setting, parameter read/write, and operation monitor commands. More Details >>
- No:21899
- Release Date:2018/08/22 16:29
-
You can select deceleration stop by setting Pr.502 (Stop mode selection at communication error). (Select from coasting to stop, deceleration to stop, and con... More Details >>
- No:21892
- Release Date:2018/08/22 16:29
-
Set Pr.338 (Operation command source) to "1" (external terminal).Set Pr.339 (Speed command source) to "0" (communication).Check the setting of Pr.79 for oper... More Details >>
- No:21869
- Release Date:2018/08/22 16:29
-
As the AS-OX has the "0ADJ" potentiometer for frequency meter calibration, use it to adjust the meter so that both readings match. More Details >>
- No:21795
- Release Date:2018/08/22 16:29
-
For the FR-E700, only the terminal FM allows for variable output and the output is a pulse signal. Therefore, it cannot be directly input to the programmable... More Details >>
- No:21682
- Release Date:2018/08/22 16:28
-
When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>
- No:21284
- Release Date:2018/08/22 16:26
-
Yes. It is available by using the FR-A7AY (plug-in option). By setting Pr.307 (Setting for zero analog output) to "20" and Pr.309 (Analog output signal volta... More Details >>
- No:21246
- Release Date:2018/08/22 16:26
-
The operation cannot be manually switched to the commercial power supply operation at an inverter fault. The operation can be automatically switched to the c... More Details >>
- No:21191
- Release Date:2018/08/22 16:26