  • Setting frequency

    Set Pr.52 (DU/PU main display data selection) to "5".This allows for displaying the setting frequency on the voltage monitor.Then, switch to the monitor mode... More Details >>

    • No:21784
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>

    • No:21915
    • Release Date:2018/08/22 16:30
  • Fault output terminal A, B, and C

    Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>

    • No:21324
    • Release Date:2018/08/22 16:27
  • Switching between external operation and NET operation

    You can switch between external operation and NET operation by turning ON/OFF the terminal X66 (RM). You can switch while Pr.79 (Operation mode) is set to "6... More Details >>

    • No:21688
    • Release Date:2018/08/22 16:28
  • NET operation mode

    Set Pr.340 (Communication startup mode selection) to "1" or "2".Also, by setting Pr.79 (Operation mode selection) to "0", "2", or "6", the inverter enters th... More Details >>

    • No:21879
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • Switching between external operation and NET operation

    You can write frequency setting by setting Pr.339 (Communication speed command source) to "0". More Details >>

    • No:21687
    • Release Date:2018/08/22 16:28
  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29
  • Operation panel

    This is because the protective function works to stop the motor. It is not a fault indication.To cancel the protective function, turn OFF the start signal an... More Details >>

    • No:21775
    • Release Date:2018/08/22 16:29
  • Operation mode setting value

    Set Pr.79 to "2" (external operation mode).    More Details >>

    • No:21818
    • Release Date:2018/08/22 16:29