FAQ within [ FREQROL-F700P ]

241-250 of Total 294

prev 25 / 30page next
  • Parameter

    Press the "MODE" key on the operation panel several times to display "P.0" and parameter setting screen. Then turn the setting dial to display "C..." screen ... More Details >>

    • No:21336
    • Release Date:2018/08/22 16:27
  • Electronic bypass function

    No, it is not available. It is only available in the External operation mode or combined operation mode (PU speed command and External operation command (Pr.... More Details >>

    • No:21192
    • Release Date:2018/08/22 16:26
  • Frequency

    It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>

    • No:21785
    • Release Date:2018/08/22 16:29
  • Display unit of operation panel

    Set the rotations per minute that is obtained while operating at the frequency set with Pr.505 (Speed setting reference) to Pr.37 (Speed display).For example... More Details >>

    • No:21774
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Since the percent value read by the calibration parameter C7 indicates that the voltage of 10 V is internally detected as 101.0%, use 101.0% as is.If you cha... More Details >>

    • No:21740
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You cannot calibrate the frequency around the middle of the current input range.The inverter determines the top and bottom points in the bias/gain adjustment... More Details >>

    • No:21736
    • Release Date:2018/08/22 16:29
  • Terminal FM

    You can connect a 1 mA full scale ammeter with internal resistance 300 Ω or lower. More Details >>

    • No:21680
    • Release Date:2018/08/22 16:28
  • Parameter setting software

    The parameter setting software we provide is the FR Configurator (FR-SW3-SETUP-WJ). You must purchase it to use. Once you purchase the software, you can upgr... More Details >>

    • No:21673
    • Release Date:2018/08/22 16:28
  • FR-PA07

    When Pr.79 is set to "3", since the start command is in the External operation mode, the RUN key of FR-PA07 does not work. More Details >>

    • No:21303
    • Release Date:2018/08/22 16:26
  • CC-Link

    Yes.You can issue operation (forward/reverse), frequency setting, parameter read/write, and operation monitor commands. More Details >>

    • No:21899
    • Release Date:2018/08/22 16:29