  • Using external potentiometer and multi-speed operation together

    You can use an external potentiometer and multi-speed operation together.When an external potentiometer signal input and multi-speed setting occur simultaneo... More Details >>

    • No:21920
    • Release Date:2018/08/22 16:30
  • Terminals P1 and P

    Removal of the jumper between the terminals P1 and P is not necessary unless you are using the DC reactor.Set Pr.30 = "0" when using the brake unit.Since set... More Details >>

    • No:21921
    • Release Date:2018/08/22 16:30
  • Frequency setting

    To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>

    • No:21799
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • Maximum frequency

    If you try to change a parameter in other than the PU operation mode, the mode specification error "Er4" may occur.Set the parameters in the PU operation mod... More Details >>

    • No:21778
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.3 (Base frequency) and Pr.18 (High speed maximum frequency) to "340 Hz", Pr.19 (Base frequency voltage) to "200 V", Pr.125 (Terminal 2 frequency setti... More Details >>

    • No:21789
    • Release Date:2018/08/22 16:29
  • CC-Link

    Slow blinking of the RUN LED indicates reverse operation.Fast blinking indicates that while the start command is input, the running frequency command is not ... More Details >>

    • No:21833
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You can use it for inverter operation, but the running speed of the inverter does not change linearly with regard to turn of the frequency setting potentiome... More Details >>

    • No:21912
    • Release Date:2018/08/22 16:30
  • Fault output terminal A, B, and C

    Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>

    • No:21324
    • Release Date:2018/08/22 16:27
  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29