  • Setting frequency

    Set Pr.52 (DU/PU main display data selection) to "5".This allows for displaying the setting frequency on the voltage monitor.Then, switch to the monitor mode... More Details >>

    • No:21784
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Change the value of Pr.18 (High speed maximum frequency).You can set any frequency within the range defined by Pr.18. More Details >>

    • No:21737
    • Release Date:2018/08/22 16:29
  • FR-A7AR E kit (Relay output function)

    Yes, you can set all of the three relay contacts to fault contacts.Set Pr.320 (RA1 output selection), 321 (RA2 output selection), and 322 (RA3 output selecti... More Details >>

    • No:21712
    • Release Date:2018/08/22 16:29
  • FR-Configurator

    If the values are already entered in the setting column, performing batch write reflects the setting on the inverter. More Details >>

    • No:21709
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>

    • No:21685
    • Release Date:2018/08/22 16:28
  • Connecting ammeter to output side

    Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>

    • No:21681
    • Release Date:2018/08/22 16:28
  • Terminal

    Signals input from the terminal 4 are not enabled if the terminal AU is not ON. For an inverter without the terminal AU, assign the AU function to an unused ... More Details >>

    • No:21679
    • Release Date:2018/08/22 16:28
  • FR-PA07

    Operations cannot be enabled separately. You only can disable or enable all the operations. More Details >>

    • No:21366
    • Release Date:2018/08/22 16:27
  • Easy setting mode

    If "HOLD" is displayed, the key lock mode enabled. Press the "MODE" key for two seconds. Then, change the setting of Pr.79 to "1". More Details >>

    • No:21350
    • Release Date:2018/08/22 16:27
  • CC-Link

    Input 4 words, output 4 words for version 1. 2, 4, and 8 times for version 2. More Details >>

    • No:21874
    • Release Date:2018/08/22 16:29