When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>
- No:21327
- Release Date:2018/08/22 16:27
-
It will be the shared type. More Details >>
- No:21331
- Release Date:2018/08/22 16:27
-
The adapter is not necessary. Only the dedicated cable FR-CB20□ is required. More Details >>
- No:21362
- Release Date:2018/08/22 16:27
-
Use Pr.903 (Frequency setting voltage gain) for setting the FR-E500. For the 700 series, use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (... More Details >>
- No:21689
- Release Date:2018/08/22 16:28
-
Set Pr.79 (Operation mode) to "3".When a signal is input to the terminal RL, the inverter starts operating at the frequency set with Pr.6 (Multi-speed settin... More Details >>
- No:21791
- Release Date:2018/08/22 16:29
-
Set the rated frequency of the motor used to it. More Details >>
- No:21814
- Release Date:2018/08/22 16:29
-
Frequency manual controller FR-AX
Considering voltage drop of the internal power supply and influence by noise, the wiring length should be 30 m or less. More Details >>
- No:21809
- Release Date:2018/08/22 16:29
-
Check that the wiring of the terminal 4 and 5 are not reversed. More Details >>
- No:21266
- Release Date:2018/08/22 16:26
-
Printing files saved in the previous version of FR-Configurator
The parameter file of FR-SW3 cannot be printed using FR-SW2. The latest version of FR-SW3 can be downloaded from the Mitsubishi Electric FA Global Website. U... More Details >>
- No:21315
- Release Date:2018/08/22 16:27
-
The first priority window of the monitor may be set to the current.When the current is displayed on the monitor (the unit is "A"), press "SET" to switch to t... More Details >>
- No:21765
- Release Date:2018/08/22 16:29