Please use the inverter optional FR-A7AY.It supports voltage output (0 to 10 VDC) and current output (0 to 20 mA DC).For the voltage output (0 to 10 VDC), th... More Details >>
- No:21812
- Release Date:2018/08/22 16:29
-
Display unit of operation panel
Set the rotations per minute that is obtained while operating at the frequency set with Pr.505 (Speed setting reference) to Pr.37 (Speed display).For example... More Details >>
- No:21774
- Release Date:2018/08/22 16:29
-
Even though the maximum frequency setting is changed using CC-Link, the running frequency is not changed. By writing the set frequency to the remote register... More Details >>
- No:21346
- Release Date:2018/08/22 16:27
-
Set Pr.55 (Frequency monitoring reference) of the first inverter to 70 Hz. More Details >>
- No:21257
- Release Date:2018/08/22 16:26
-
Automatic restart after instantaneous power failure
The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>
- No:21255
- Release Date:2018/08/22 16:26
-
With the automatic bypass sequence (Pr.139 ≠ 9999, Pr.159 = 9999), the motor operation is switched to commercial power supply operation when the output frequ... More Details >>
- No:21189
- Release Date:2018/08/22 16:26
-
The signals MRS and CS are required when the automatic bypass sequence enabled. More Details >>
- No:21187
- Release Date:2018/08/22 16:26
-
Set Pr.340 (Communication startup mode selection) to other than "0".Also, set Pr.79 (Operation mode) to "0", "2", or "6".Powering the inverter on automatical... More Details >>
- No:21903
- Release Date:2018/08/22 16:30
-
You can select deceleration stop by setting Pr.502 (Stop mode selection at communication error). (Select from coasting to stop, deceleration to stop, and con... More Details >>
- No:21892
- Release Date:2018/08/22 16:29
-
No problem. The inverter actually occupies the reserved bits and does not use them. More Details >>