Start main contents

Factory Automation

FAQ

Factory Automation

FAQAbout Products

  • Font Size
  • S
  • M
  • L

FAQ within [ FREQROL-F700P ]

261-270 of Total 295

prev 27 / 30page next
  • CC-Link

    The FR-A7NC is required. ("FR-A7NC-E kit" for the FR-E700 series. The FR-E700-NC CC-Link communication type does not require an option.) More Details >>

    • No:21668
    • Release Date:2018/08/22 16:28
  • CC-Link

    When configuring the inverter via communication such as CC-Link, some signals still requires to be input from the external terminals.(Terminal OH: External t... More Details >>

    • No:21888
    • Release Date:2018/08/22 16:29
  • Start command, speed command

    You can do so by setting Pr.339 (Communication speed command source) = 1 (external).   More Details >>

    • No:21881
    • Release Date:2018/08/22 16:29
  • CC-Link

    Input 4 words, output 4 words for version 1. 2, 4, and 8 times for version 2. More Details >>

    • No:21874
    • Release Date:2018/08/22 16:29
  • CC-Link

    Use Pr.542 to set the station number and Pr.543 to set the baud rate.To set the baud rate to 10 Mbps, set Pr.543 to "4". More Details >>

    • No:21839
    • Release Date:2018/08/22 16:29
  • CC-Link

    1. It depends on how Pr.338 (Communication operation command source) and Pr.339 (Communication speed command source) are set.2. The external terminal reset i... More Details >>

    • No:21838
    • Release Date:2018/08/22 16:29
  • CC-Link

    The FR-A7NC is designed for the FR-A700, FR-F700, and FR-F700P.The FR-A7NC E kit is designed for the FR-E700 with the dedicated cover. (Only the dedicated co... More Details >>

    • No:21830
    • Release Date:2018/08/22 16:29
  • CC-Link

    You can check the fault records with Pr.544 (CC-Link extended setting) set to "12" for double setting.Set H74 for the instruction code and turn ON RYF. More Details >>

    • No:21829
    • Release Date:2018/08/22 16:29
  • CC-Link

    You cannot monitor the running frequency and conveyor speed (machine speed) simultaneously.The inverter does not have a function to output them simultaneously. More Details >>

    • No:21827
    • Release Date:2018/08/22 16:29
  • CC-Link

    Yes. More Details >>

    • No:21713
    • Release Date:2018/08/22 16:29

261-270 of Total 295