FAQ within [ FREQROL-F700P ]
-
Set Pr.56 (Current monitor reference) to "10A". More Details >>
- No:21865
- Release Date:2018/08/22 16:29
-
If Pr.340 (Communication startup mode selection) and Pr.79 (Operation mode selection) are set so that the inverter starts CC-Link operation from power-on and... More Details >>
- No:21840
- Release Date:2018/08/22 16:29
-
Slow blinking of the RUN LED indicates reverse operation.Fast blinking indicates that while the start command is input, the running frequency command is not ... More Details >>
- No:21833
- Release Date:2018/08/22 16:29
-
Check if the master station uses CC-Link Version 1 and the FR-A7NC uses CC-Link Version 2. More Details >>
- No:21831
- Release Date:2018/08/22 16:29
-
You can check the fault records with Pr.544 (CC-Link extended setting) set to "12" for double setting.Set H74 for the instruction code and turn ON RYF. More Details >>
- No:21829
- Release Date:2018/08/22 16:29
-
You cannot monitor the running frequency and conveyor speed (machine speed) simultaneously.The inverter does not have a function to output them simultaneously. More Details >>
- No:21827
- Release Date:2018/08/22 16:29
-
Turn ON the monitor command RYC. More Details >>
- No:21826
- Release Date:2018/08/22 16:29
-
Set Pr.79 to "2" (external operation mode). More Details >>
- No:21818
- Release Date:2018/08/22 16:29
-
External installationRated current
Since the external thermal prevents the motor from being overheated, install it between the output terminal of the inverter and the motor.The rated current i... More Details >>
- No:21817
- Release Date:2018/08/22 16:29
-
For low-speed operation, perform auto tuning and use (Advanced) magnetic flux vector control. More Details >>
- No:21810
- Release Date:2018/08/22 16:29