FAQ


FAQAbout Products

- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F700P
FAQ
Keyword Search
FAQ within [ FREQROL-F700P ]
-
Set Pr.79 (Operation mode) to "3" and Pr.161 (Frequency setting/key lock operation selection) to "1". More Details >>
- No:21249
- Release Date:2018/08/22 16:26
-
Pr.338 is for the communication operation command source at communication operation and specifies the command source to supply the start signal.Pr.339 is for... More Details >>
- No:21880
- Release Date:2018/08/22 16:29
-
External installationRated current
Since the external thermal prevents the motor from being overheated, install it between the output terminal of the inverter and the motor.The rated current i... More Details >>
- No:21817
- Release Date:2018/08/22 16:29
-
No, we have no cable 50 cm long. The optional cables 1 m, 3 m, and 5 m long are available. (1 m: FR-CB201, 3 m: FR-CB203, 5 m: FR-CB205) More Details >>
- No:21365
- Release Date:2018/08/22 16:27
-
It is not stored in a parameter but memorized as the frequency setting value after acceleration by the acceleration signal.You can also choose whether or not... More Details >>
- No:21733
- Release Date:2018/08/22 16:29
-
FR-A7AR E kit (Relay output function)
Yes, you can set all of the three relay contacts to fault contacts.Set Pr.320 (RA1 output selection), 321 (RA2 output selection), and 322 (RA3 output selecti... More Details >>
- No:21712
- Release Date:2018/08/22 16:29
-
Use the FR-A740. Basically, select the capacity according to the calculation result of "rated inverter output current ? rated motor current × 1.1". More Details >>
- No:21244
- Release Date:2018/08/22 16:26
-
The way to monitor the output current and read parameters via CC-Link is identical in all operation modes. More Details >>
- No:21872
- Release Date:2018/08/22 16:29
-
The start commands cannot be input from both sources simultaneously because the operation command source is specified.You can switch the command source as ne... More Details >>
- No:21828
- Release Date:2018/08/22 16:29
-
Automatic restart after instantaneous power failure
The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>
- No:21255
- Release Date:2018/08/22 16:26