  • Electronic bypass function

    For countermeasures against the open/close surge of the MC (magnetic contactor). Insert a diode not to apply 27 VDC or more to the open collector terminal of... More Details >>

    • No:21188
    • Release Date:2018/08/22 16:26
  • CC-Link

    It is OK if stations are set as reserved. More Details >>

    • No:21868
    • Release Date:2018/08/22 16:29
  • CC-Link

    The start commands cannot be input from both sources simultaneously because the operation command source is specified.You can switch the command source as ne... More Details >>

    • No:21828
    • Release Date:2018/08/22 16:29
  • CC-Link

    Yes. Set the first monitor code in the lower 8 bits and the second monitor code in the upper 8 bits of RWwn.Set H6F to the first monitor code, and H70 to the... More Details >>

    • No:21824
    • Release Date:2018/08/22 16:29
  • Electronic bypass function

    No, it cannot be normally closed contact. When the electronic bypass function is used, the setting of Pr.17 is disabled. More Details >>

    • No:21193
    • Release Date:2018/08/22 16:26
  • CC-Link

    Yes. The FR-A7NC E kit contains a dedicated front cover since its size changes by the installed board.You can additionally purchase the FR-A7NC E kit cover o... More Details >>

    • No:21889
    • Release Date:2018/08/22 16:29
  • CC-Link

    Up to 42 units can be connected. (When only inverters are connected) More Details >>

    • No:21873
    • Release Date:2018/08/22 16:29
  • FR-A5AY

    The FR-A5AY cannot be used in the FR-A700 (F700(P)). It cannot be installed due to the difference of the connector shape. More Details >>

    • No:21260
    • Release Date:2018/08/22 16:26
  • CC-Link

    You can set reserved and invalid stations.The Instruction Manual instructs to set consecutive numbers because the master regards an empty number as an error. More Details >>

    • No:21905
    • Release Date:2018/08/22 16:30
  • CC-Link

    Yes.You can issue operation (forward/reverse), frequency setting, parameter read/write, and operation monitor commands. More Details >>

    • No:21899
    • Release Date:2018/08/22 16:29