Set Pr.71 (Applied motor), Pr.80 (Motor capacity), Pr.81 (Number of motor poles), and Pr.800 (Control method selection). More Details >>
- No:21245
- Release Date:2018/08/22 16:26
-
Connect the wire to the optional FR-A7NC's terminal block. (The terminal block is detachable.) More Details >>
- No:21875
- Release Date:2018/08/22 16:29
-
Use the FR-A740. Basically, select the capacity according to the calculation result of "rated inverter output current ? rated motor current × 1.1". More Details >>
- No:21244
- Release Date:2018/08/22 16:26
-
You can select deceleration stop by setting Pr.502 (Stop mode selection at communication error). (Select from coasting to stop, deceleration to stop, and con... More Details >>
- No:21892
- Release Date:2018/08/22 16:29
-
No problem. The inverter actually occupies the reserved bits and does not use them. More Details >>
- No:21890
- Release Date:2018/08/22 16:29
-
Pr.30 = "1" and Pr.70 = "0". More Details >>
- No:21143
- Release Date:2018/08/22 16:26
-
Create a ladder program to read inverter faults on the programmable controller.Set the instruction code (H74-H77) and turn ON the instruction code execution ... More Details >>
- No:21886
- Release Date:2018/08/22 16:29
-
For the FR-E700, only the terminal FM allows for variable output and the output is a pulse signal. Therefore, it cannot be directly input to the programmable... More Details >>
- No:21682
- Release Date:2018/08/22 16:28
-
With the automatic bypass sequence (Pr.139 ≠ 9999, Pr.159 = 9999), the motor operation is switched to commercial power supply operation when the output frequ... More Details >>
- No:21189
- Release Date:2018/08/22 16:26
-
The start commands cannot be input from both sources simultaneously because the operation command source is specified.You can switch the command source as ne... More Details >>
- No:21828
- Release Date:2018/08/22 16:29