Operations cannot be enabled separately. You only can disable or enable all the operations. More Details >>
- No:21366
- Release Date:2018/08/22 16:27
-
When Pr.79 is set to "3", since the start command is in the External operation mode, the RUN key of FR-PA07 does not work. More Details >>
- No:21303
- Release Date:2018/08/22 16:26
-
You cannot monitor the running frequency and conveyor speed (machine speed) simultaneously.The inverter does not have a function to output them simultaneously. More Details >>
- No:21827
- Release Date:2018/08/22 16:29
-
This subroutine is to check the data link status and needs to be executed only once at the start of the program. More Details >>
- No:21767
- Release Date:2018/08/22 16:29
-
It is not recommended to start and stop the inverter with the electromagnetic contactor (MC). This will accelerate the deterioration (due to the inrush curre... More Details >>
- No:21322
- Release Date:2018/08/22 16:27
-
Set Pr.55 (Frequency monitor reference) to "100 Hz".If the indication of the installed frequency meter does not match the running frequency, use the calibrat... More Details >>
- No:21768
- Release Date:2018/08/22 16:29
-
Since the percent value read by the calibration parameter C7 indicates that the voltage of 10 V is internally detected as 101.0%, use 101.0% as is.If you cha... More Details >>
- No:21740
- Release Date:2018/08/22 16:29
-
Yes. More Details >>
- No:21713
- Release Date:2018/08/22 16:29
-
Yes. It is available by using the FR-A7AY (plug-in option). By setting Pr.307 (Setting for zero analog output) to "20" and Pr.309 (Analog output signal volta... More Details >>
- No:21246
- Release Date:2018/08/22 16:26
-
CC-Link station number setting
Change the setting in the PU operation mode. More Details >>
- No:21747
- Release Date:2018/08/22 16:29