- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F700P
FAQ
Keyword Search
FAQ within [ FREQROL-F700P ]
-
For the inverter, the option card FR-A7NC is necessary. More Details >>
- No:21897
- Release Date:2018/08/22 16:29
-
You can select deceleration stop by setting Pr.502 (Stop mode selection at communication error). (Select from coasting to stop, deceleration to stop, and con... More Details >>
- No:21892
- Release Date:2018/08/22 16:29
-
Display unit of operation panel
Set the rotations per minute that is obtained while operating at the frequency set with Pr.505 (Speed setting reference) to Pr.37 (Speed display).For example... More Details >>
- No:21774
- Release Date:2018/08/22 16:29
-
The FR-A5AY cannot be used in the FR-A700 (F700(P)). It cannot be installed due to the difference of the connector shape. More Details >>
- No:21260
- Release Date:2018/08/22 16:26
-
No, it cannot be normally closed contact. When the electronic bypass function is used, the setting of Pr.17 is disabled. More Details >>
- No:21193
- Release Date:2018/08/22 16:26
-
No, it is not available. It is only available in the External operation mode or combined operation mode (PU speed command and External operation command (Pr.... More Details >>
- No:21192
- Release Date:2018/08/22 16:26
-
The operation cannot be manually switched to the commercial power supply operation at an inverter fault. The operation can be automatically switched to the c... More Details >>
- No:21191
- Release Date:2018/08/22 16:26
-
Set Pr.79 (Operation mode) setting value to "0", "2", or "6", Pr.340 (Communication startup mode selection) other than the setting value, Pr.542 (Station num... More Details >>
- No:21896
- Release Date:2018/08/22 16:29
-
Pr.338 is for the communication operation command source at communication operation and specifies the command source to supply the start signal.Pr.339 is for... More Details >>
- No:21880
- Release Date:2018/08/22 16:29
-
Automatic restart after instantaneous power failure
The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>
- No:21255
- Release Date:2018/08/22 16:26