FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F700P
FAQ
Keyword Search
FAQ within [ FREQROL-F700P ]
-
You can connect up to three inverters to a single external frequency setting potentiometer to control them. More Details >>
- No:21917
- Release Date:2018/08/22 16:30
-
Set Pr.338 (Communication command source) to "0" to give a start command from "NET". Set Pr.339 (Speed command source) to "1" to make a frequency setting fro... More Details >>
- No:21285
- Release Date:2018/08/22 16:26
-
Reverse rotation prevention selection
Yes, it does. When the inverter is coasting in the reverse direction, it starts in the reverse direction and switches to the forward rotation after a deceler... More Details >>
- No:21125
- Release Date:2018/08/22 16:26
-
Normally, the inverter starts up in the NET operation mode at power ON when Pr.340 is set to "10" and Pr.79 is set to "0". When it starts up in the PU operat... More Details >>
- No:21319
- Release Date:2018/08/22 16:27
-
The first priority window of the monitor may be set to the current.When the current is displayed on the monitor (the unit is "A"), press "SET" to switch to t... More Details >>
- No:21765
- Release Date:2018/08/22 16:29
-
Printing files saved in the previous version of FR-Configurator
The parameter file of FR-SW3 cannot be printed using FR-SW2. The latest version of FR-SW3 can be downloaded from the Mitsubishi Electric FA Global Website. U... More Details >>
- No:21315
- Release Date:2018/08/22 16:27
-
Check that the wiring of the terminal 4 and 5 are not reversed. More Details >>
- No:21266
- Release Date:2018/08/22 16:26
-
Frequency manual controller FR-AX
Considering voltage drop of the internal power supply and influence by noise, the wiring length should be 30 m or less. More Details >>
- No:21809
- Release Date:2018/08/22 16:29
-
Set the rated frequency of the motor used to it. More Details >>
- No:21814
- Release Date:2018/08/22 16:29
-
Set Pr.79 (Operation mode) to "3".When a signal is input to the terminal RL, the inverter starts operating at the frequency set with Pr.6 (Multi-speed settin... More Details >>
- No:21791
- Release Date:2018/08/22 16:29