Not possible.Instead of FR-DU07, use FR-PA07 (or FR-PU07) as an operation panel for FR-E700. More Details >>
- No:21708
- Release Date:2018/08/22 16:29
-
The power supply voltage may have dropped.Read the converter output voltage monitor (Pr.55 = 8) and check if Converter output voltage monitor/√2 is within th... More Details >>
- No:21820
- Release Date:2018/08/22 16:29
-
Pr.30 = "1" and Pr.70 = "0". More Details >>
- No:21143
- Release Date:2018/08/22 16:26
-
No, it cannot be normally closed contact. When the electronic bypass function is used, the setting of Pr.17 is disabled. More Details >>
- No:21193
- Release Date:2018/08/22 16:26
-
For countermeasures against the open/close surge of the MC (magnetic contactor). Insert a diode not to apply 27 VDC or more to the open collector terminal of... More Details >>
- No:21188
- Release Date:2018/08/22 16:26
-
Not available. Differences between the parts supplied with the FR-A7NC and FR-A7NC E kit will result in improper installation. Use the FR-A7NC. Use the FR-A7NC. More Details >>
- No:21258
- Release Date:2018/08/22 16:26
-
No, it does not run. "Err" is displayed when it is operated. Always input the same voltage (400 V) to the main power supply and control power supply. More Details >>
- No:21179
- Release Date:2018/08/22 16:26
-
After setting Pr.79 (Operation mode selection) to "2" and Pr.340 (Communication startup mode selection) to "10", reset the inverter (or power ON again) to st... More Details >>
- No:21256
- Release Date:2018/08/22 16:26
-
Turn ON and OFF the RES signal to enable the inverter-driven operation. More Details >>
- No:21190
- Release Date:2018/08/22 16:26
-
Use Pr.542 to set the station number and Pr.543 to set the baud rate.To set the baud rate to 10 Mbps, set Pr.543 to "4". More Details >>
- No:21839
- Release Date:2018/08/22 16:29