FAQ within [ FREQROL-F700P ]

291-295 of Total 295

prev 30 / 30page next
  • CC-Link communication

    After setting Pr.79 (Operation mode selection) to "2" and Pr.340 (Communication startup mode selection) to "10", reset the inverter (or power ON again) to st... More Details >>

    • No:21256
    • Release Date:2018/08/22 16:26
  • Automatic restart after instantaneous power failure

    The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>

    • No:21255
    • Release Date:2018/08/22 16:26
  • DC reactor

    The 75K or higher DC reactor is included in the 75K or higher inverter. The option cannot be purchased separately. More Details >>

    • No:21252
    • Release Date:2018/08/22 16:26
  • Frequency command

    Since the initial value of Pr.13 (Starting frequency) is 0.5 Hz, the operation does not start unless 0.5 Hz or higher frequency is set. When 0.49 Hz is set i... More Details >>

    • No:21251
    • Release Date:2018/08/22 16:26
  • Replacement

    The station number and baud rate were set using the dial for the FR-A5NC, but parameter is used for the FR-A7NC. Pr.542 (Communication station number (CC-Lin... More Details >>