  • Terminals P1 and P

    Removal of the jumper between the terminals P1 and P is not necessary unless you are using the DC reactor.Set Pr.30 = "0" when using the brake unit.Since set... More Details >>

    • No:21921
    • Release Date:2018/08/22 16:30
  • Output voltage

    Since the output frequency was measured, it is considered that the start signal was input correctly.Check the output voltage on the voltage monitor of the in... More Details >>

    • No:21780
    • Release Date:2018/08/22 16:29
  • Multi-speed setting and external potentiometer

    The multi-speed setting is prioritized.The external potentiometer setting is effective when the multi-speed signal is not input. More Details >>

    • No:21773
    • Release Date:2018/08/22 16:29
  • Current setting

    Yes.The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current s... More Details >>

    • No:21770
    • Release Date:2018/08/22 16:29
  • Package

    It is the fixing screw for the inverter cooling fan cover.The size and number of screws depend on the model and capacity.(When exporting the product to the E... More Details >>

    • No:21746
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Pr.1 (Maximum frequency) and Pr.18 (Maximum frequency).   More Details >>

    • No:21744
    • Release Date:2018/08/22 16:29
  • Electromagnetic contactor

    Turning ON/OFF the output side during operation causes open/close surges that may trigger the protective function (against overcurrent or overvoltage) of the... More Details >>

    • No:21725
    • Release Date:2018/08/22 16:29
  • Operation panel

    If "PS" is displayed even the "STOP/RESET" key on the operation panel is not pressed, a inverter fault may be the cause. In this case, consult with your sale... More Details >>

    • No:21343
    • Release Date:2018/08/22 16:27
  • Wiring the terminal

    There is no problem with the wiring. Keep the rating (24 VDC, 0.1 A) of the terminal PC. More Details >>

    • No:21342
    • Release Date:2018/08/22 16:27
  • Countermeasure against noises

    Yes. The carrier frequency can be decreased by the setting of Pr.72 (PWM frequency selection). More Details >>

    • No:21338
    • Release Date:2018/08/22 16:27