FAQ within [ FREQROL-F700P ]
-
Yes. More Details >>
- No:21871
- Release Date:2018/08/22 16:29
-
With the automatic bypass sequence (Pr.139 ≠ 9999, Pr.159 = 9999), the motor operation is switched to commercial power supply operation when the output frequ... More Details >>
- No:21189
- Release Date:2018/08/22 16:26
-
Yes.The inverter requires the start signal and frequency setting signal. More Details >>
- No:21793
- Release Date:2018/08/22 16:29
-
Yes. Set the first monitor code in the lower 8 bits and the second monitor code in the upper 8 bits of RWwn.Set H6F to the first monitor code, and H70 to the... More Details >>
- No:21824
- Release Date:2018/08/22 16:29
-
Use Pr.542 to set the station number and Pr.543 to set the baud rate.To set the baud rate to 10 Mbps, set Pr.543 to "4". More Details >>
- No:21839
- Release Date:2018/08/22 16:29
-
No, it cannot be normally closed contact. When the electronic bypass function is used, the setting of Pr.17 is disabled. More Details >>
- No:21193
- Release Date:2018/08/22 16:26
-
The detection time 1 s cannot be changed. More Details >>
- No:21277
- Release Date:2018/08/22 16:26
-
Yes. The carrier frequency can be decreased by the setting of Pr.72 (PWM frequency selection). More Details >>
- No:21338
- Release Date:2018/08/22 16:27
-
Since Pr.125 (Terminal 2 frequency setting gain frequency) is initially set to 60 Hz, change it to 85 Hz. More Details >>
- No:21907
- Release Date:2018/08/22 16:30
-
Calibrate C6 (Pr.904) (Terminal 4 frequency setting bias frequency) and C7 (Pr.905) (Terminal 4 frequency setting gain frequency). If the situation does not ... More Details >>
- No:21265
- Release Date:2018/08/22 16:26