  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29
  • FR-Configurator

    The FR Configurator FR-SW3-SETUP-WJ can only allow for test operation.Since this is a tool to support the system launch and maintenance, it is not designed f... More Details >>

    • No:21914
    • Release Date:2018/08/22 16:30
  • Frequency setting

    When turning the setting dial to set the frequency, press the "SET" key while the desired value blinks. (The setting frequency and "F" flicker alternately.) More Details >>

    • No:21742
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Yes, you can set Pr.20 to 20 Hz. More Details >>

    • No:21683
    • Release Date:2018/08/22 16:28
  • Supported model for FR-Configurator

    The FR-E700 is not supported by FR-SW2-SETUP-WJ. The FR-E700 series are supported by FR-SW3-SETUP-WJ. This software can be downloaded from the Mitsubishi Ele... More Details >>

    • No:21314
    • Release Date:2018/08/22 16:26
  • CC-Link

    Set Pr.340 (Communication startup mode selection) to other than "0".Also, set Pr.79 (Operation mode) to "0", "2", or "6".Powering the inverter on automatical... More Details >>

    • No:21903
    • Release Date:2018/08/22 16:30
  • Parameter setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) to "50 Hz".Set Pr.1 (Maximum frequency) to "50 Hz". More Details >>

    • No:21720
    • Release Date:2018/08/22 16:29
  • FR-Configurator

    If the values are already entered in the setting column, performing batch write reflects the setting on the inverter. More Details >>

    • No:21709
    • Release Date:2018/08/22 16:29
  • Network operation

    Set Pr.338 to "0" (NET) and Pr.339 to "1" or "2". More Details >>

    • No:21674
    • Release Date:2018/08/22 16:28
  • Megger test

    When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>

    • No:21327
    • Release Date:2018/08/22 16:27