Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>
- No:21286
- Release Date:2018/08/22 16:26
-
Up to 30 m. (To avoid noise and voltage drop) More Details >>
- No:21910
- Release Date:2018/08/22 16:30
-
The inverter has the calibration function.Use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (Terminal 2 frequency setting gain) for calibrat... More Details >>
- No:21849
- Release Date:2018/08/22 16:29
-
This parameter cannot be changed in the external operation mode.Change Pr.77 (Parameter write selection) to "2" before changing the setting of Pr.72. More Details >>
- No:21743
- Release Date:2018/08/22 16:29
-
It cannot be avoided by using parameters. More Details >>
- No:21724
- Release Date:2018/08/22 16:29
-
Electronic thermal O/L relay setting
When using multiple motors, connect an external thermal for each of them. Set Pr.9 to "0" to disable the function. (When multiple motors are present, it is n... More Details >>
- No:21676
- Release Date:2018/08/22 16:28
-
Yes. The carrier frequency can be decreased by the setting of Pr.72 (PWM frequency selection). More Details >>
- No:21338
- Release Date:2018/08/22 16:27
-
To set the motor to coasting state, the following methods are available: 1. Set Pr.250 (Stop selection) to "0" and turn OFF the start command. 2. Short the t... More Details >>
- No:21271
- Release Date:2018/08/22 16:26
-
Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>
- No:21909
- Release Date:2018/08/22 16:30
-
The frequency can be set to 65 Hz with the initial setting.Check if Pr.1 (Maximum frequency) is set to 60 Hz. More Details >>
- No:21858
- Release Date:2018/08/22 16:29