FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F700P
FAQ
Keyword Search
FAQ within [ FREQROL-F700P ]
-
Yes.The inverter requires the start signal and frequency setting signal. More Details >>
- No:21793
- Release Date:2018/08/22 16:29
-
In this case, the JOG operation is prioritized.When the terminals JOG and SD are short-circuited and turned ON, the frequency setting by the external potenti... More Details >>
- No:21804
- Release Date:2018/08/22 16:29
-
Set the rated frequency of the motor used to it. More Details >>
- No:21814
- Release Date:2018/08/22 16:29
-
Check if the master station uses CC-Link Version 1 and the FR-A7NC uses CC-Link Version 2. More Details >>
- No:21831
- Release Date:2018/08/22 16:29
-
If Pr.544 (CC-Link extended setting) is set to other than "0", you do not need to change Pr.544 (CC-Link extended setting).Write the extended setting of the ... More Details >>
- No:21834
- Release Date:2018/08/22 16:29
-
When the frequency is set using the setting dial, it is not necessary to set it again.The inverter memorizes the setting value internally even after the powe... More Details >>
- No:21842
- Release Date:2018/08/22 16:29
-
Use Pr.542 (Station number). More Details >>
- No:21876
- Release Date:2018/08/22 16:29
-
With the automatic bypass sequence (Pr.139 ≠ 9999, Pr.159 = 9999), the motor operation is switched to commercial power supply operation when the output frequ... More Details >>
- No:21189
- Release Date:2018/08/22 16:26
-
Turn ON and OFF the RES signal to enable the inverter-driven operation. More Details >>
- No:21190
- Release Date:2018/08/22 16:26
-
When Pr.80 and Pr.81 are set to the value other than "9999", control other than V/F control is performed. For the FR-F700(P) FR-D700, and FR-F700PJ, Pr.81 is... More Details >>
- No:21259
- Release Date:2018/08/22 16:26
61-70 of Total 294