FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F700P
FAQ
Keyword Search
FAQ within [ FREQROL-F700P ]
-
Yes. It is available by using the FR-A7AY (plug-in option). By setting Pr.307 (Setting for zero analog output) to "20" and Pr.309 (Analog output signal volta... More Details >>
- No:21246
- Release Date:2018/08/22 16:26
-
Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>
- No:21280
- Release Date:2018/08/22 16:26
-
1. Yes. 2. The standard set by Pr.56. More Details >>
- No:21669
- Release Date:2018/08/22 16:28
-
1. Set Pr.162 to "10" (Frequency search at every start).2. You can ignore the setting if the motor excitation current is unknown. More Details >>
- No:21718
- Release Date:2018/08/22 16:29
-
No. You cannot change the setting during operation.However, setting Pr.77 (Parameter write selection) to "2" allows for the setting change during operation. ... More Details >>
- No:21734
- Release Date:2018/08/22 16:29
-
This subroutine is to check the data link status and needs to be executed only once at the start of the program. More Details >>
- No:21767
- Release Date:2018/08/22 16:29
-
Set the rated frequency of the motor used to it. More Details >>
- No:21814
- Release Date:2018/08/22 16:29
-
Yes. However, write the setting data to the RAM of the inverter.Set RWw1 in the setting value and turn ON the frequency setting command RYD.To continuously s... More Details >>
- No:21825
- Release Date:2018/08/22 16:29
-
You can use optional items, such as enclosure surface operation panel FR-PA07 and parameter unit FR-PU07.Use the PU connector of the inverter for connection.... More Details >>
- No:21832
- Release Date:2018/08/22 16:29
-
Use Pr.542 to set the station number and Pr.543 to set the baud rate.To set the baud rate to 10 Mbps, set Pr.543 to "4". More Details >>
- No:21839
- Release Date:2018/08/22 16:29
61-70 of Total 295