  • Frequency setting

    Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>

    • No:21685
    • Release Date:2018/08/22 16:28
  • Electronic thermal O/L relay setting

    When using multiple motors, connect an external thermal for each of them. Set Pr.9 to "0" to disable the function. (When multiple motors are present, it is n... More Details >>

    • No:21676
    • Release Date:2018/08/22 16:28
  • NET operation mode

    Set Pr.340 (Communication startup mode selection) to "1" or "2".Also, by setting Pr.79 (Operation mode selection) to "0", "2", or "6", the inverter enters th... More Details >>

    • No:21879
    • Release Date:2018/08/22 16:29
  • Frequency setting

    This parameter cannot be changed in the external operation mode.Change Pr.77 (Parameter write selection) to "2" before changing the setting of Pr.72. More Details >>

    • No:21743
    • Release Date:2018/08/22 16:29
  • Printing files saved in the previous version of FR-Configurator

    The parameter file of FR-SW3 cannot be printed using FR-SW2. The latest version of FR-SW3 can be downloaded from the Mitsubishi Electric FA Global Website. U... More Details >>

    • No:21315
    • Release Date:2018/08/22 16:27
  • Frequency

    When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>

    • No:21284
    • Release Date:2018/08/22 16:26
  • Frequency setting

    When using the setting dial to set the frequency, turn the dial and display the frequency. Then, press the "SET" key while the desired value flickers.The fre... More Details >>

    • No:21848
    • Release Date:2018/08/22 16:29
  • Frequency setting

    The calibration parameter C6 (Terminal 4 frequency setting bias) is initially set to "20%". Therefore, voltage input to the terminal 4 does not become effect... More Details >>

    • No:21806
    • Release Date:2018/08/22 16:29
  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29
  • Terminal

    Signals input from the terminal 4 are not enabled if the terminal AU is not ON. For an inverter without the terminal AU, assign the AU function to an unused ... More Details >>

    • No:21679
    • Release Date:2018/08/22 16:28