FAQ within [ FREQROL-F700P ]

71-80 of Total 294

prev 8 / 30page next
  • Replacement

    It is Pr.125 (Terminal 2 frequency setting gain frequency). Adjust the slope with C4 (903) (Terminal 2 frequency setting gain) as necessary. More Details >>

    • No:21247
    • Release Date:2018/08/22 16:26
  • Input/output voltage

    The output voltage will not be imbalanced when the inverter is used. (Since AC is converted into DC and then into AC, the output voltage is hardly effected f... More Details >>

    • No:21278
    • Release Date:2018/08/22 16:26
  • External operation

    The inverter has the calibration function.Use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (Terminal 2 frequency setting gain) for calibrat... More Details >>

    • No:21849
    • Release Date:2018/08/22 16:29
  • Brake resistor

    Use high-duty brake resistor FR-ABR-2.2K. (Shared with the 1.5K inverter.) More Details >>

    • No:21330
    • Release Date:2018/08/22 16:27
  • FR-PA07

    Since the multi-speed is given a higher priority, the setting by the setting dial is not enabled unless all of the multi-speed signals are OFF. More Details >>

    • No:21302
    • Release Date:2018/08/22 16:26
  • Parameter setting

    Set Pr.55 (Frequency monitor reference) to "100 Hz".If the indication of the installed frequency meter does not match the running frequency, use the calibrat... More Details >>

    • No:21768
    • Release Date:2018/08/22 16:29
  • Parameter setting

    Yes. The single-phase 200 V can be input. If the single-phase input is performed when Pr.872 (Input phase loss protection) is set to "1", the input phase los... More Details >>

    • No:21270
    • Release Date:2018/08/22 16:26
  • Frequency setting signal

    Calibrate C6 (Pr.904) (Terminal 4 frequency setting bias frequency) and C7 (Pr.905) (Terminal 4 frequency setting gain frequency). If the situation does not ... More Details >>

    • No:21265
    • Release Date:2018/08/22 16:26
  • NET operation mode

    Set Pr.340 (Communication startup mode selection) to "1" or "2".Also, by setting Pr.79 (Operation mode selection) to "0", "2", or "6", the inverter enters th... More Details >>

    • No:21879
    • Release Date:2018/08/22 16:29
  • Control terminal

    You also need to set Pr.79 (Operation mode) to "3". More Details >>

    • No:21844
    • Release Date:2018/08/22 16:29