FAQ within [ FREQROL-F700P ]
-
Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>
- No:21788
- Release Date:2018/08/22 16:29
-
Press the "SET" key once while the output frequency is monitored.The unit indicator LED changes from "Hz" to "A" and the monitor display changes to the current. More Details >>
- No:21764
- Release Date:2018/08/22 16:29
-
Set Pr.52 (PU/DU main display data selection) to "5".Set the monitor as the third monitor, frequency -> current -> setting frequency. More Details >>
- No:21745
- Release Date:2018/08/22 16:29
-
Even while the inverter is operating, you can use the setting dial to change the frequency and then press the SET key and the inverter operates at the new fr... More Details >>
- No:21739
- Release Date:2018/08/22 16:29
-
No. You cannot check the accumulated number of rotations on the monitor. More Details >>
- No:21715
- Release Date:2018/08/22 16:29
-
Yes, you can set Pr.20 to 20 Hz. More Details >>
- No:21683
- Release Date:2018/08/22 16:28
-
Connecting ammeter to output side
Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>
- No:21681
- Release Date:2018/08/22 16:28
-
Normally, Pr.80 and Pr.81 are the parameters that can be changed when the operation is stopped in the PU operation mode. The "Er4" is a mode designation erro... More Details >>
- No:21335
- Release Date:2018/08/22 16:27
-
It will be the shared type. More Details >>
- No:21331
- Release Date:2018/08/22 16:27
-
Calibrate the terminal 2 bias. More Details >>